CHAPTER 5 PARAMETERS
E5CK
5--22
Input type
•
Match the setting (software) of this parameter with the setting (hardware) of the
input type jumper connector.
•
Set the input types to be connected to terminal Nos. 6 to 8 by the input type codes in
the table below.
•
Set the code according to the following table. Default is “2: K1 thermocouple”.
Set value
Input Type
Jumper Position
0
JPt
-199.9 to 650.0 (
_
C)
/-199.9 to 999.9 (
_
F)
Platinum resis-
TC PT
1
Pt
-199.9 to 650.0 (
_
C)
/-199.9 to 999.9 (
_
F)
Platinum resis
tance thermometer
TC
⋅
PT
2
K1
-200 to 1300 (
_
C)
/-300 to 2300 (
_
F)
3
K2
0.0 to 500.0 (
_
C)
/0.0 to 900.0 (
_
F)
4
J1
-100 to 850 (
_
C)
/-100 to 1500 (
_
F)
5
J2
0.0 to 400.0 (
_
C)
/0.0 to 750.0 (
_
F)
6
T
-199.9 to 400.0 (
_
C)
/-199.9 to 700.0 (
_
F)
7
E
0 to 600 (
_
C)
/0 to 1100 (
_
F)
8
L1
-100 to 850 (
_
C)
/-100 to 1500 (
_
F)
9
L2
0.0 to 400.0 (
_
C)
/0.0 to 750.0 (
_
F)
Thermocouple
TC
⋅
PT
10
U
-199.9 to 400.0 (
_
C)
/-199.9 to 700.0 (
_
F)
Thermocouple
TC
⋅
PT
11
N
-200 to 1300 (
_
C)
/-300 to 2300 (
_
F)
12
R
0 to 1700 (
_
C)
/0 to 3000 (
_
F)
13
S
0 to 1700 (
_
C)
/0 to 3000 (
_
F)
14
B
100 to 1800 (
_
C)
/300 to 3200 (
_
F)
15
W
0 to 2300 (
_
C)
/0 to 4100 (
_
F)
16
PL
II
0 to 1300 (
_
C)
/0 to 2300 (
_
F)
17
4 to 20mA
Current input
I
18
0 to 20mA
Current input
I
19
1 to 5V
20
0 to 5V
Voltage input
V
21
0 to 10V
Voltage input
V
F
Related article
3.2 Setting Input Specifications (page 3-3)
F
Related parameters
When input type is set to temperature input:
“
_
C/
_
F selection” (setup mode)
When input type is set to voltage input or current input:
“Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
Setup Mode
Function
Comment
See