E5CK
5--23
Scaling upper limit
Scaling lower limit
Decimal point
Conditions of Use
The input type must be set to analog input
(voltage or current input).
•
This parameter can be used only when voltage input or current input is selected as
the input type.
•
When voltage input or current input is selected as the input type, scaling is carried
out. Set the scaling upper limit in the “scaling upper limit” parameter and the scaling
lower limit in the “scaling lower limit” parameter.
•
The “decimal point” parameter specifies the decimal point position of parameters
(set point, etc.) whose unit is set to EU (Engineering Unit).
•
Scaling upper limit, Scaling lower limit
Parameter
Setting Range
Unit
Default
Scaling upper limit
Scaling lower limit +1 to 9999
EU
100
Scaling lower limit
-1999 to scaling upper limit -1
EU
0
•
Decimal point : default : 0
Set Value
Setting
Example
0
1
2
3
0 digits past decimal point
1 digit past decimal point
2 digits past decimal point
3 digits past decimal point
1234
123.4
12.34
1.234
F
Related article
3.2 Setting Input Specifications (page 3-3)
F
Related parameter
“Input type” (setup mode)
Parameter initialize
•
Returns parameter settings to their defaults. However, note that the following
parameters are not affected by execution of this parameter:
“input type”, “scaling upper limit”, “scaling lower limit”, “decimal point” and
“
_
C/
_
F selection”.
•
When this parameter is selected, [
] (“no”) is first displayed. To initialize parame-
ters, press the
key to specify [
] (“yes”).
Setup Mode
Function
Comment
See
Function
Example
of use