CHAPTER 5 PARAMETERS
E5CK
5--24
_
C/
_
F selection
Conditions of Use
The input type must be set to temperature
input (thermocouple or platinum resis-
tance thermometer).
•
This parameter can be used when thermocouple or platinum resistance thermometer
is selected as the input type.
•
Set the temperature input unit to either of “
_
C” or “
_
F”.
Setting Range
Default
:
_
C /
:
_
F
F
Related article
3.2 Setting Input Specifications (page 3-3)
F
Related parameter
“Input type” (setup mode)
Control output 1 assignment
Control output 2 assignment
•
Assigns the output functions to either of control output 1 or 2.
•
The following six output functions can be assigned as outputs:
Control output (heat), Control output (cool), Alarms 1 to 3, and LBA.
•
Errors 1 and 2 cannot be assigned as outputs.
•
When the output function assigned to control output 1 is ON, the OUT1 LED lights.
However, note that the OUT1 LED does not light when control output (heat) or control
output (cool) are assigned to linear outputs such as current and voltage.
•
When the output function assigned to control output 2 is ON, the OUT2 LED lights.
Symbol
Function
Control output (heat)
Control output (cool)
Alarm 1 Alarm 2 Alarm 3
LBA
Defaults:
“Control output 1” = [
], “Control output 2” = [
]
F
Related article
3.3 Setting Output Specifications (page 3-5)
F
Related parameters
•
Alarm-related parameters
•
Heating and cooling related parameter
“LBA detection time” (level 2 mode)
Setup Mode
Function
Comment
See
Function
Comment
See