Auxiliary output 1 assignment
•
Assigns output functions to auxiliary output 1. The following six output functions
can be assigned as outputs:
Alarms 1 to 3, LBA, Error 1 (input error), and Error 2 (A/D converter error).
•
Control output (heat) and control output (cool) cannot be assigned as outputs.
•
When the output function assigned to auxiliary output 1 is ON, the SUB1 LED lights.
Symbol
Function
Alarm 1
Alarm 2
Alarm 3
LBA
Error 1
Error 2
Defaults: [
]
F
Related article
3.3 Setting Output Specifications (page 3-5)
F
Related parameter
•
Alarm-related parameter
“LBA detection time” (level 2 mode)
Alarm 1 type
Alarm 2 type
Alarm 3 type
Conditions of Use
Alarms must be assigned as outputs. For
example, if alarm outputs 1 and 2 only are
assigned as outputs, the ”alarm 3 type”
parameter cannot be used.
•
“Alarm 1 to 3 type” parameters specify the operation of the alarm by the one of the
set values in the following table. For details of operation at an alarm, see page 3-7.
Set Value
Settings
Set Value
Settings
1
Upper-and lower-limit alarm
(deviation)
7
Lower-limit alarm with standby
sequence (deviation)
2
Upper-limit alarm (deviation)
8
Absolute-value upper-limit alarm
3
Lower-limit alarm (deviation)
9
Absolute-value lower-limit alarm
4
Upper-and lower-limit range alarm
(deviation)
10
Absolute-value upper-limit alarm with
standby sequence
5
Upper-and lower-limit alarm with
standby sequence (deviation)
11
Absolute-value lower-limit alarm with
standby sequence
6
Upper-limit alarm with standby
sequence (deviation)
Defaults: Deviation upper limit
F
Related article
3.4 Setting Alarm Type (page 3-7)
F
Related parameters
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode)
“Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode)
“Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Control
output 1 assignment” “Control output 2 assignment” (setup mode)
Setup Mode
Function
Comment
See
Function
Comment
See