CHAPTER 5 PARAMETERS
E5CK
5--28
Set point upper limit
Set point lower limit
•
Limits the upper and lower limits of the set point. When the set point exceeds the set-
tings of the “Set point upper limit” and “Set point lower limit” parameters, the E5CK
controller regards the settings of the “Set point upper limit” and “Set point lower
limit” parameters as the set points.
•
When the input type is changed to temperature input, the set point upper and lower
limits are changed to the upper and lower limits of the currently selected sensor. And
when the input type is changed to analog input, the set point upper and lower limits
are changed to the scaling upper and lower limits.
•
During temperature input, the decimal point position is dependent on the currently
selected sensor, and during analog input on the results of scaling.
Parameter
Setting Range
Unit
Default
SP setting upper limit
SP setting lower limit +1 to scaling upper limit
EU
1300
SP setting lower limit
Scaling lower limit to SP setting upper limit -1
EU
-200
During temperature input, the range becomes the range of use of the selected sensor
instead of the scaling upper and lower limit values.
F
Related article
4.2 Operating Condition Restrictions (page 4-5)
F
Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
PID / ON/OFF
•
Selects advanced PID control or ON/OFF control.
Setting Range
Default
: advance PID/
:ON/OFF
F
Related article
4.1 Selecting the Control Method (page 4-3)
F
Related parameters
“Hysteresis (heat)” “Hysteresis (cool)” (level 1 mode)