E5CK
5--29
ST
ST stable range
Conditions of Use
The input type must be set to temperature
input, and the control must be either stan-
dard control or advanced PID control.
•
When the “ST” parameter is set to “ON”, the self-tuning (ST) function is active. Dur-
ing operation of the ST function, the power on the load side connected to the control
output must be turned ON at the same time or before start of E5CK operation.
•
The “ST stable range” parameter sets the stable range width during self-tuning.
However, note that this parameter cannot be used when the “ST” parameter is set to
“OFF”.
Parameter
Setting Range
Unit
Default
ST
: ST function OFF/
: ST function ON
None
ST stable range
0.1 to 999.9
_
C or
_
F
15.0
F
Related article
Fuzzy self-tuning (page A-10)
F
Related parameters
“Input type” (setup mode)
“PID / ON/OFF” (expansion mode)
α
Conditions of Use
The control must be advanced PID con-
trol, and ST must be set to OFF.
•
Sets advanced PID-control parameter
α
.
Setting Range
Unit
Default
0.00 to 1.00
None
0.65
F
Related parameter
“PID / ON/OFF” (expansion mode)