E5CK
5--31
Automatic return of display mode
•
If you do not operate any of the controller keys for the time set in this parameter when
in levels 0 to 2 modes, the display automatically returns to the PV/SP display.
•
When this parameter is set to “0”, this function is disabled.
•
This parameter is invalid while the menu is displayed.
Setting Range
Unit
Default
0 to 99
Second
0
AT hysteresis
Conditions of Use
The control must be advanced PID con-
trol, and ST must be set to OFF.
•
The levels of limit cycle operations during AT execution are given hysteresis at event
ON/OFF switching. This parameter sets this hysteresis width.
Setting Range
Unit
Default
0.1 to 9.9
%FS
0.2
LBA detection width
Conditions of Use
The LBA (Loop Break Alarm) function
must be assigned as an output.
•
This parameter can be used when LBA is assigned as an output.
•
When the change width of the manipulated variable is below the width set in this
parameter, the controller regards this as detection of an LBA.
Setting Range
Unit
Default
0.0 to 999.9
%FS
0.2
Expansion Mode
Function
Comment
Function
Comment
Function
Comment