CHAPTER 5 PARAMETERS
E5CK
5--34
Communication stop bit
Communication data length
Communication parity
Communication baud rate
Communication unit No.
Conditions of Use
The communications function must be in
use.
•
These parameters set the communications conditions. Make sure that the stop bit,
data length, parity and baud rate of the host computer and the E5CK controller are
matching. These parameters are valid when the power is turned ON again or when
level 0 to 2 modes are switched.
•
When connecting two or more E5CK controllers to the host computer, set unit Nos.
that will not conflict with the unit Nos. of other controllers.
•
“Communication stop bit” parameter
Setting Range
Unit
Default
1, 2
Bits
2
•
“Communication data length” parameter
Setting Range
Unit
Default
7, 8
Bits
7
•
“Communication parity” parameter
Setting
Default
: None/
:Even/
:Odd
•
“Communication baud rate” parameter
Setting Range
Unit
Default
1.2, 2.4, 4.8, 9.6, 19.2
kbps
9.6
•
“Communication unit No.” parameter
Setting Range
Unit
Default
0 to 99
None
0
F
Related article
Capter 6 Using the Communications Function (page 6-1)
F
Related parameter
“Remote/Local” (level 2 mode)
F
Option unit
RS-232C unit (E53-CK01), RS-485 unit (E53-CK03)
Option Mode
Function
Comment
See
Model