CHAPTER 5 PARAMETERS
E5CK
5--36
•
The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0”. When selecting this mode for the first time after the E5CK
has left the factory, return the “security” parameter to “0”.
•
This mode contains the parameters for user calibration of inputs and outputs. Only
parameters relating to input types specified in the “input type” parameter (setup
mode) can be used. Also, related output parameters can be used only when the com-
munications unit (E53-CKF) is added on.
•
To select this mode when in the levels 0 to 2, setup, expansion and option modes, press
the
key for 1 second minimum. The display changes to the menu display. If you
select [
] using the
key then press the
key for 1 second minimum,
the controller enters the calibration mode.
•
For details on parameters in the calibration mode, see 4.5 Calibration (page 4-11).
Calibration Mode