Parameter Operation Lists
A-9
Appendices
■
Initial Setting Level (1)
Parameters
Mode
indicators/
displayed
text
Setting (monitor) value
Default
Unit
Set
value
0: No
PV auto reset
SP mode
100’s digit
1: Yes
0 None
PV/SP display
Tuning selection
0 ST/AT
1 ST
2
PV
→
SP
AT
3 ST/AT
4 ST
5
SP
→
PV
AT
6 ST/AT
7 ST
8
No PV display
AT
PV/SP display
Tuning selection
SP mode
10’s digit
9 PV
→
SP
ST/AT
0 None
ST executing
display
Manual reset
enable/
disable
Control period
selection
0 2/20
(s)
1
Disabled
6/60
2 2/20
3
Enabled
Enabled
6/60
4 2/20
5
Disabled
6/60
6 2/20
7
Disabled
Enabled
6/60
8 2/20
ST executing display
Manual reset
enable/disable
Control period selection
SP mode
1’s digit
9
Enabled Disabled
6/60
0 None
Integral time setting unit
ALM mode
100’s digit
0: Second
1: Minute
0 None
0: 0% FS
1: 0.05% FS
2: 0.1% FS
3: 0.2% FS
4: 0.3% FS
5: 0.5% FS
6: 0.75% FS
7: 1% FS
8: 1.5% FS
Hysteresis width
ALM mode
10’s digit
9: 2% FS
3
*1
None
0: 0% FS
1:
±
0.1% FS
2:
±
0.25% FS
3:
±
0.5% FS
4:
±
0.75% FS
5: ±
1% FS
6: ±
1.25% FS
7:
±
1.5% FS
8:
±
1.75% FS
Temperature width in
which the deviation
indicator lights
ALM mode
1’s digit
9:
±
2% FS
5
*2
None
ST stable range
IS mode
1 to 999
15
°
C/
°
F
*1.
The default is 2, however, for multi-input (thermocouple/platinum resistance thermometer) models.
*2.
The default is 2, however, for multi-input (thermocouple/platinum resistance thermometer) models.