E5CS-X

E5CS-X

12

Precautions

Mounting

All Temperature Controllers in the E5CS-X Series conform to
DIN43700 standard.
The recommended panel thickness is 1 to 4 mm.

Flush Mounting

Insert the Temperature Controller, back end first, into the hole of the
mounting panel. Mount the adapter by pushing it forward from the
back of the Temperature Controller. Push the adapter as close as
possible to the front panel of the Temperature Controller to eliminate
the gap between them. Then, secure the adapter with screws as
shown in the figure below.

Removal

Loosen the screws on the adapter and push the hook open to re-
move the adapter.

Hook

Screw

Environment

Do not install the Temperature Controller in locations subject to dust
or corrosive gases. Do not install the Temperature Controller in loca-
tions subject to heavy vibrations or shocks, splashes of water or oil,

or high temperatures.
Separate the Temperature Controller from equipment that gener-
ates strong, high-frequency noise such as high-frequency welders.

Connection Examples

Solderless Terminal
Use M3.5 solderless terminals with the Temperature Controller’s
M3.5 self-rising pressure plate screws.

Solder-dipped Lead Wires
Strip the lead wire 6 to 12 mm and carefully arrange the wire tip.

Do not tighten the terminal screw with excessive force.

Input Sensor Connection

The lead wires connecting the sensor to the Temperature Controller
must be separated from power lines and load lines wherever pos-
sible, to prevent them from being induced by noise.
Use the specified compensating conductors for the thermocouple
type Temperature Controllers.
Use lead wires with a small resistance for the Platinum resistance
thermometer type Temperature Controllers.

Sequence Circuit

Several seconds are required until the relay is turned ON after pow-
er is supplied to the Temperature Controller. Therefore, take this
time lag into consideration when designing a sequence circuit which
incorporates the Temperature Controller.

OMRON Corporation

Industrial Automation Company

Measuring and Supervisory Controls Division
28th Fl., Crystal Tower Bldg.,
1-2-27, Shiromi, Chuo-ku,
Osaka 540-6028 Japan
Tel: (81)6-6949-6035/Fax: (81)6-6949-606

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. H032-E1-2A In the interest of product improvement, specifications are subject to change without notice.

Printed in Japan
0300-0.3M (0689) 

a

Summary of Contents for E5CS-X -

Page 1: ...n alarm available Nonvolatile memory Field selectable control mode ON OFF or PID Ordering Information Thermocouple Type Input K CA Chromel alumel J IC Iron constantan Standard temperature ranges switch selectable In ut 1 000 900 800 700 600 500 400 300 200 100 0 0 200 0 300 0 400 0 500 0 600 0 999 0 999 0 200 0 300 0 400 0 500 Set no 0 1 2 3 4 5 6 6 7 8 9 Temperature unit selectable C C C F C F C ...

Page 2: ...u a a Voltage output E5CS QGX With alarm Relay output E5CS R1GX a a Voltage output E5CS Q1GX The functions can be factory set for shipment as shown in the table below depending on the suffix attached to the model number when you place your order Two suffixes are selectable DIN or F Example E5CS RKJX DIN Suffix Suffix None DIN F Standard temperature K CA J IC 2 0 to 400 8 0 to 400 2 0 to 400 S a da...

Page 3: ...ive Cover Y92A 48 The protective cover protects the front panel particularly the setting section against dust dirt and water drip It also prevents the set values from being altered due to accidental contact with the setting keys Y92A 48 Protective Cover ...

Page 4: ...mation Proportional period 2 20 seconds Sampling period 500 ms Output change period 2 seconds Indication change period 2 seconds Insulation resistance 20 MΩ min at 500 VDC Dielectric strength 2 000 VAC 50 60 Hz for 1 minute between current carrying terminals of different polarity Vibration resistance Malfunction 2 to 55 Hz 2 G for 10 minutes each in X Y and Z directions Destruction 10 to 55 Hz 0 7...

Page 5: ...d and downward setting keys by holding down hidden protection key Main Display Sequentially displays the present temperature set temperature and an alarm value in that order each time the temperature indication switching key is pressed Control Output Indicator Lights while the control output is be ing produced Alarm Output Operation Indicator Lights when the alarm output relay is energized Upward ...

Page 6: ...ange selector switch Alarm mode selector switch Right side view Temperature unit C or F where a choice is available is selected using pin 6 of the internal DIP switch which is also used for other set tings such as the control mode and sensor compensation Internal DIP switch Left side view The procedures for making actual settings are given below Setting the Temperature Range Set the desired temper...

Page 7: ... Setting enabled ON Setting disabled OFF Temperature sensor DIN ON sensor standard JIS OFF Scale indicator F ON indicator selectable C OFF Setting the Alarm Mode The desired alarm mode can be chosen from one of the eight alarm modes using the alarm mode selector switch as shown below Switch setting Mode Alarm output 0 9 No alarm function OFF 1 Upper and lower limit alarms 2 Upper limit alarm 3 Low...

Page 8: ...onds ON 1 6 5 4 3 2 P X ON Determining Control Output Operation If the Temperature Controller is used to control a heater the control output can be set to perform reverse inverted operation Set pin 3 of the control output mode selector switch to OFF Reverse output ON OFF Set temperature ON 1 6 5 4 3 2 P X ON Conversely if the Temperature Controller is used to control a cool ing device such as a fr...

Page 9: ...shift value can be set within a range of 99 to 99 except with a 0 0 to 99 9 platinum resistance thermometer where the input shift narrows to a range of 9 9 to 9 9 When the desired shift has been entered set pin 4 to OFF The input shift value remains in memory Consequently if the input shift func tion is not needed with pin 4 activated set the input shift value to 0 Sensor Failure Operation Thermoc...

Page 10: ...itive and negative of thermocouple have been reversed 3 Temperature has fallen to a value much smaller than the set temperature range OFF E11 or E33 see note 1 Memory failure E11 or A D converter failure E33 has occurred Temperature Controller must be repaired if normal operation is not restored by turning power OFF once and ON again Both control output and alarm output are OFF Note 1 The key oper...

Page 11: ...nel cutout Note 1 The recommended panel thickness is 1 to 4 mm 2 The Temperature Controller is contained in a mount ing bracket so close side by side Temperature Controller mounting is possible Provide a center to center distance of at least 60 mm between two adja cent Temperature Controllers ...

Page 12: ...g pressure plate screws Solder dipped Lead Wires Strip the lead wire 6 to 12 mm and carefully arrange the wire tip Do not tighten the terminal screw with excessive force Input Sensor Connection The lead wires connecting the sensor to the Temperature Controller must be separated from power lines and load lines wherever pos sible to prevent them from being induced by noise Use the specified compensa...

Reviews: