E5CS-X

E5CS-X

44

J

SELECTING ALARM MODES

Select one of the eight alarm modes by using the rotary DIP
switch located next to the rotary DIP switch for temperature scale
range selection. The following table shows alarm functions. The
selector switch is factory-set to position 2, upper-limit alarm.

Switch setting

Mode

Alarm output

Notes

0, 9

No alarm

OFF

When the alarm mode selector switch is 0 or 9,
neither the alarm value is displayed nor the AL
indicator lights even when the return key is pressed.

1

Upper- and lower-limit alarms

Alarm value setting range X may be 0 to full scale.

If the alarm value is shifted outside the temperature

2

Upper-limit alarm

If the alarm value is shifted outside the temperature
scale range as a result of changing the scale range, it
is automatically changed to the maximum value of the
newly set scale range.

3

Lower-limit alarm

4

Upper- and lower-limit range alarm

5

Upper- and lower-limit alarms with
standby sequence

6

Upper-limit alarm with standby
sequence

7

Lower-limit alarm with standby
sequence

8

Absolute-value alarm

Alarm value setting range Y must be within the
temperature scale range.

Standby Sequence

Alarm functions with standby sequence suppress nuisance
alarms when the controller is first powered up. As shown in the
temperature charts at right, the alarm output is suppressed until
the temperature exceeds the alarm band or alarm limit one time.

When temperature rises from the set temperature

Upper-limit alarm

Set temperature

Lower-limit alarm

Alarm output

ON

OFF

When temperature falls below the set temperature

Upper-limit alarm

Set temperature

Lower-limit alarm

Alarm output

ON

OFF

J

SETTING KEY PROTECTION

Protect against unauthorized changes in temperature values by
disabling the operation of Up and Down keys. Set function
selector DIP switch “P” to ON. To enable changes from the front
panel, simultaneously press the hidden write protection key
(lower left corner) with the Up and Down keys. If the internal
protection switch is set to OFF, changes can be made simply by
pressing the Up and Down keys.

ON

1

6

5

4

3

2

P

X

ON

Summary of Contents for E5CS

Page 1: ...D Pt 100 Ω DIN and JIS standards Interchangeable thermistor THE types Output Contact E5CS R1KJX F E5CS R1PX F E5CS R1GX F Voltage E5CS Q1KJX F E5CS Q1PX F E5CS Q1GX F Temperature Ranges Thermocouple Input Type Input type Type K Type J Temperature range 0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500 Scale indication C C C F C F C F C F F C C C F C...

Page 2: ...dication accuracy 0 5 of full scale 1 digit max Display range 999 to 999 limited to input type Control Type ON OFF and PID with automatic tuning of proportional band switch selectable modes Proportional band 3 to 20 in PID mode automatically adjusted according to the rise time of the controlled system Reset time 4 minutes in PID mode Rate time 0 4 minutes in PID mode Proportional period 2 or 20 se...

Page 3: ... to OFF changes can be made simply by pressing the Up and Down keys 5 Down key decreases the set temperature or alarm value when pressed Decreases the value quickly when held down 8 Display data identifier lights SP when the set temperature is displayed on the main display and AL when an alarm value is displayed 6 Return key changes the value displayed on the main display each time pressed 9 Red d...

Page 4: ...al mechanism Alarm mode selector switch Protection switch Right side view Control mode selector switch Left side view Temperature range selector switch Select the desired temperature range by using the temperature range selector switch rotary DIP type The other rotary DIP switch is used to select one of eight alarm functions Be sure the set temperature and alarm values are within the new range Oth...

Page 5: ...l output ON OFF Set temperature Switch 1 OFF Temperature controller performs ON OFF action ON 1 6 5 4 3 2 P X ON Control output ON OFF Set temperature Switch 3 ON Used for cooling operations in ON OFF action ON 1 6 5 4 3 2 P X ON PID Action Set switch 1 of the function selector DIP switch to ON to perform PID control action Follow the steps described below Determining Proportional Period Set switc...

Page 6: ...e main display Then set the shift value by using the Up or Down key Switch 4 ON Input shift function enabled ON 1 6 5 4 3 2 P X ON Fine adjustment of the temperature indication and the resulting controlled temperature is possible without changing or affecting the set point The input shift value can be set within the range from 99 9 to 99 F or C For ranges that have resolution to 0 1 the input shif...

Page 7: ... 0 1 2 3 4 5 6 7 8 Temperature range 50 to 50 0 0 to 50 0 20 to 80 0 0 to 99 9 0 to 200 0 to 300 0 to 400 0 to 600 0 to 800 Scale indication C C C C F C F C C F F F Unit of measure 1 C or F 0 1 C or F 1 C or F 0 1 C or F 1 C or F Note 1 Do not set the selector switch to position 9 This will cause error message FFF or to be displayed 2 When changing scale ranges where the unit of measure changes 1 ...

Page 8: ...dby sequence 6 Upper limit alarm with standby sequence 7 Lower limit alarm with standby sequence 8 Absolute value alarm Alarm value setting range Y must be within the temperature scale range Standby Sequence Alarm functions with standby sequence suppress nuisance alarms when the controller is first powered up As shown in the temperature charts at right the alarm output is suppressed until the temp...

Page 9: ...ing heating reverse operation OFF during cooling normal operation fff blinks 1 Failure has occurred in thermocouple or platinum RTD 2 Temperature has risen much beyond scale range OFF blinks 1 Failure has occurred in platinum RTD 2 Polarities positive and negative of thermocouple are reversed 3 Temperature has fallen much below scale range OFF e11 or e33 1 Memory failure E11 display 2 Analog to di...

Page 10: ...splashes of water or oil and high temperatures Separate the temperature controller from equipment that generates strong high frequency electrical noise such as welding equipment Sensor Input Connections The lead wires connecting the platinum RTD to the temperature controller must be separated from the power lines an the load lines wherever possible to prevent them from being inducted by electrical...

Reviews: