2
Temperature Controllers
E5CSZ
Ordering Information
■
List of Models
Note: Modules are available with a black case. Add the suffix “-B” to models with a black case.
■
Accessories (Order Separately)
Protective Cover
Terminal Cover
Specifications
■
Ratings
Size
Power supply
voltage
Number of
alarm points
Control output
TC/Pt multi-input
Case color: Light gray
1/16 DIN
48
×
48
×
78 mm
(W
×
H
×
D)
100 to 240 VAC
0
Relay
E5CSZ-RT
Voltage (for driving SSR)
E5CSZ-QT
1
Relay
E5CSZ-R1T
Voltage (for driving SSR)
E5CSZ-Q1T
24 VAC/VDC
0
Relay
E5CSZ-RTD
Voltage (for driving SSR)
E5CSZ-QTD
1
Relay
E5CSZ-R1TD
Voltage (for driving SSR)
E5CSZ-Q1TD
Type
Model
Hard Protective Cover
Y92A-48B
Model
E53-COV10
Supply voltage
100 to 240 VAC, 50/60 Hz
24 VAC/VDC, 50/60 Hz
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
5 VA
3 VA/2 W
Sensor input
Multi-input (thermocouple/platinum resistance thermometer) type: K, J, L, Pt100
Control
output
Relay output
SPST-NO, 250 VAC, 3A (resistive load)
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Control method
ON/OFF or 2-PID (with auto-tuning)
Alarm output
SPST-NO, 250 VAC, 1A (resistive load)
Setting method
Digital setting using front panel keys
Indication method
3.5 digit, 7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions
•
Setting change prohibit (key protection)
•
Input shift
•
Temperature unit change (
°
C/
°
F)
•
Direct/reverse operation
•
Temperature range, Sensor switching (K/J/L, Pt100)
•
Switching is performed between a thermocouple and platinum resistance thermometer for multi-input models.
•
Control period switching
•
8-mode alarm output
•
Sensor error detection
Ambient temperature
−
10 to 55
°
C (with no condensation or icing)
Ambient humidity
25% to 85%
Storage temperature
−
25 to 65
°
C (with no condensation or icing)