Multipoint Temperature Controller
E5ZE-8
@D1@B-V2
5
Note: 1. The measurement accuracy of the E5ZE used with a thermocouple B at 400
°
C or 750
°
F max. is not guaranteed. The following measure-
ment accuracy values are applied to the E5ZE.
K and T at –100
°
C max. and U:
±
3
°
C
±
1 digit max.
K and T at –100
°
F max. and U:
±
5.4
°
F
±
1 digit max.
R, S, and W at 200
°
C max., and B at 1,000
°
C max.:
±
4
°
C
±
1 digit max.
R, S, and W at 400
°
F max., and B at 1,800
°
F max.:
±
7.2
°
F
±
1 digit max.
2. The measurement accuracy of the E5ZE used with any thermocouple is 1
°
C/
°
F. The thermocouple can be used under the following tem-
perature ranges to increase the measurement accuracy to as high as 0.1
°
C/
°
F.
K thermocouple:
0.0
°
C to 1,300.0
°
C, 0.0
°
F to 2,300.0
°
F
T or U thermocouple:
0.0
°
C to 400.0
°
C, 0.0
°
F to 700.0
°
F
N thermocouple:
400.0
°
C to 1,300.0
°
C, 700.0
°
F to 2,300.0
°
F
J, E, L, or PLII thermocouple: Any temperature
3. Upper limit is 3000.0
°
C/
°
F when set from CompoBus/D.
■
Communications Specifications
Conforming to DeviceNet Communications Protocol
For details, refer to the CompoBus/D (DeviceNet) Operation Manual (W267) and the E5ZE-8 Communication Manual (H114).
Note: 1. An external terminator must be attached.
2. Indicates the distance between nodes farthest from each other.
3. The maximum network length is 100 m if a thin dedicated cable is applied to the trunk line.
!NOTICE
This product has been tested by ODVA’s authorized Independent
Test Lab and found to comply with ODVA Conformance Test Soft-
ware Version A-13.
For the specifications of objects in details, refer to the E5ZE-8 Com-
munication Manual (H114).
DeviceNet Communications Items
Note: Items for the OUT side of remote I/O are not included.
Dimensions
With casing: 173.5 x 253 x 65 mm max.
Enclosure rating
IP00
Weight
With casing:1,700 g max.
Connection method
Multi-drop or T-branching (see note 1)
Baud rate
500/250/125 kbps
Communications media
Dedicated 5-wire cable (with 2 communications wires, 2 power wires, and 1 shield wire)
Communications distance
Baud rate
Maximum network length (see note 2)
Branch line length
Total branch line length
500 kbps
100 m max. (see note 3)
6 m max.
39 m max.
250 kbps
250 m max. (see note 3)
6 m max.
78 m max.
125 kbps
500 m max. (see note 3)
6 m max.
156 m max.
Remote I/O points
IN: 14 / OUT: 9
Error control
CRC error and node address duplication check
Remote I/O communications
IN:
PV (process value) (8 points), Alarms 1 and 2 status, AT status, HB alarm status,
HS alarm status, and error status
OUT:
RUN/STOP and SP (set point) (8 points)
Explicit message communications
All read and write parameters (See note.)