background image

Multipoint Temperature Controller

 E5ZE-8

@D1@B-V2

5

Note: 1. The measurement accuracy of the E5ZE used with a thermocouple B at 400

°

C or 750

°

F max. is not guaranteed. The following measure-

ment accuracy values are applied to the E5ZE.
K and T at –100

°

C max. and U:

±

3

°

±

1 digit max.

K and T at –100

°

F max. and U:

±

5.4

°

±

1 digit max.

R, S, and W at 200

°

C max., and B at 1,000

°

C max.:

±

4

°

±

1 digit max.

R, S, and W at 400

°

F max., and B at 1,800

°

F max.:

±

7.2

°

±

1 digit max.

2. The measurement accuracy of the E5ZE used with any thermocouple is 1

°

C/

°

F. The thermocouple can be used under the following tem-

perature ranges to increase the measurement accuracy to as high as 0.1

°

C/

°

F.

K thermocouple:

0.0 

°

C to 1,300.0 

°

C, 0.0 

°

F to 2,300.0 

°

T or U thermocouple: 

0.0 

°

C to 400.0 

°

C, 0.0 

°

F to 700.0 

°

F

N thermocouple: 

400.0 

°

C to 1,300.0 

°

C, 700.0 

°

F to 2,300.0 

°

F

J, E, L, or PLII thermocouple: Any temperature

3. Upper limit is 3000.0

°

C/

°

F when set from CompoBus/D.

Communications Specifications

Conforming to DeviceNet Communications Protocol

For details, refer to the CompoBus/D (DeviceNet) Operation Manual (W267) and the E5ZE-8 Communication Manual (H114).

Note: 1. An external terminator must be attached.

2. Indicates the distance between nodes farthest from each other.

3. The maximum network length is 100 m if a thin dedicated cable is applied to the trunk line.

 !NOTICE

This product has been tested by ODVA’s authorized Independent
Test Lab and found to comply with ODVA Conformance Test Soft-
ware Version A-13.
For the specifications of objects in details, refer to the E5ZE-8 Com-
munication Manual (H114)
.

DeviceNet Communications Items

Note: Items for the OUT side of remote I/O are not included.

Dimensions

With casing: 173.5 x 253 x 65 mm max.

Enclosure rating

IP00

Weight

With casing:1,700 g max.

Connection method

Multi-drop or T-branching (see note 1)

Baud rate

500/250/125 kbps

Communications media

Dedicated 5-wire cable (with 2 communications wires, 2 power wires, and 1 shield wire)

Communications distance

Baud rate

Maximum network length (see note 2)

Branch line length

Total branch line length

500 kbps

100 m max. (see note 3)

6 m max.

39 m max.

250 kbps

250 m max. (see note 3)

6 m max.

78 m max.

125 kbps

500 m max. (see note 3)

6 m max.

156 m max.

Remote I/O points

IN: 14 / OUT: 9 

Error control

CRC error and node address duplication check

Remote I/O communications

IN:

PV (process value) (8 points), Alarms 1 and 2 status, AT status, HB alarm status, 
HS alarm status, and error status

OUT:

RUN/STOP and SP (set point) (8 points)

Explicit message communications

All read and write parameters (See note.)

Summary of Contents for E5ZE-8 D1 B-V2

Page 1: ...re inputs Model Number Structure Model Number Legend 1 Number of Control Points 8 8 channels 2 Control Method A Standard heating or cooling V Heating and cooling 3 Control Output Heating Side Q Voltage output for driving SSR C Current output 4 Heater Burnout and SSR Failure Detection See note 1 H Available A Not available 5 Communications Function D1 DeviceNet 6 Input TC Thermocouple P Platinum re...

Page 2: ... Current Transformers CT Special Cables Recommended Power Supplies No of control points Control method Control output Heater burnout and SSR failure detection Input type Thermocouple Platinum resistance thermometer 8 Standard see note 1 Voltage Available see note 2 E5ZE 8AQHD1TCB V2 E5ZE 8AQHD1PB V2 Current Not available E5ZE 8ACAD1TCB V2 E5ZE 8ACAD1PB V2 Heating and cooling Voltage Available see ...

Page 3: ...VDC max OFF leakage current 1 mA DC max Alarm outputs Temperature alarm The total output of all control points alarm 1 NPN open collector output and alarm 2 NPN open collector output HB alarm heater burnout detection Total output of all control points 1 point NPN open collector output HS alarm SSR failure detection Total output of all control points 1 point NPN open collector output Temperature co...

Page 4: ... for ON OFF control only in units of 0 1 C F Cooling coefficient 0 0 to 10 0 in units of 0 1 Proportional band 0 0 to 999 9 C F in units of 0 1 C F Cooling side Cooling coefficient Proportional band Integral reset time 0 to 3 999 s in units of 1 s for both heating and cooling Derivative rate time 0 to 3 999 s in units of 1 s for both heating and cooling Control period Heating side 1 to 99 s in uni...

Page 5: ...the distance between nodes farthest from each other 3 The maximum network length is 100 m if a thin dedicated cable is applied to the trunk line NOTICE This product has been tested by ODVA s authorized Independent Test Lab and found to comply with ODVA Conformance Test Soft ware Version A 13 For the specifications of objects in details refer to the E5ZE 8 Com munication Manual H114 DeviceNet Commu...

Page 6: ...le Platinum resistance thermometer E5ZE 8 D1 B V2 E5ZE CBL200 E5ZE CBL200 E5ZE CBL200 XW2D 20G6 Connector Terminal Conversion Unit XW2D 20G6 Connector Terminal Conversion Unit G7TC OC08 G7TC OC16 I O Block G70D V O 16 Relay terminal Host Unit Compatible with Explicit Message Communications OMRON s C200HW DRM21 EV1 CVM1 DRM21 EV1 and CS1W DRM21 Note When replacing with an E5ZE 8 D1 B part of the la...

Page 7: ... up otherwise operating errors may result Prepare four M4 screws to mount the E5ZE to control panels Use flat washers and spring washers with screws to mount the E5ZE to control panels so that the screws will not loosen The mounting brackets must be attached to the E5ZE with the four M3 6 screws provided with the E5ZE and each of the screws should be tightened to a torque of 0 43 to 0 58 N m or 4 ...

Page 8: ... CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards codes or regulations that apply to the combination of products in the customer s application or use of the products At t...

Reviews: