117
Programless Communications
Section 5-6
5-6-5
Operation Command Codes for Programless Communications
The following functions are executed using operation commands.
Command codes for programless communications operation commands differ
from command codes in CompoWay/F communications because the data
length is limited to 16 bits.
Example Calculation of Operation Command Codes for Programless
Communications
Any channel between 1 and 64 or all channels can be selected.
Structure of
Operation Command
Codes for
Programless
Communications
• Write Mode
• Software Reset
• Run
• Stop
• Manual
• Auto
• GT Execute
• GT Cancel
• AT Execute
• AT Cancel
• Bank 0 Change to
Bank 3 Change
• Reset Error
• Alarm 1 to Alarm 3
Latch Cancel
• All Alarm Latch
Cancel
• Save RAM Data
• Register Unit Con-
figuration
Unit No.
Channel
Operation command
Operation command code
(hexadecimal)
All units
All channels Run
2808
Stop
2C08
Manual
3008
Auto
3408
GT Execute
4408
GT Execute
4808
Bit position
Meaning
0
Not used. (3 bits)
1
Related information (2 bits)
2
3
All channels specified (1 bit)
4
Unit specification (6 bits)
5
6
7
8
9
10
Command code (6 bits)
11
12
13
14
15
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......