174
Sensor Input Ranges
Appendix
Sensor Input Ranges
• Applicable standards by input type are as follows:
K,J,T,E,N,R,S,B: JIS C1602-1995
L: Fe-CuNi,
DIN43710-1985
U: Cu-CuNi,
DIN43710-1985
W:
W5Re/W26Re, ASTM E988-1990
PLII:
According to Platinel II Electromotive Force Table by Engelhard Corp.
JPt100:
JIS C1604-1989, JIS C1606-1989
Pt100: JIS
C1604-1997,
IEC751
Input type
Specifica-
tion
Set value
Setting range
Indication range
°
C
°
F
°
C
°
F
T
e
m
p
e
ratur
e in
put
s
Platinum
resistance
thermome-
ters
Pt100
0
−
200 to 850
−
300 to 1500
−
220 to 870
−
340 to 1540
1
−
199.9 to 500.0
−
199.9 to 900.0
−
219.9 to 520.0
−
239.9 to 940.0
2
0.0 to 100.0
0.0 to 210.0
−
20.0 to 120.0
−
40.0 to 250.0
JPt100
3
−
199.9 to 500.0
−
199.9 to 900.0
−
219.9 to 520.0
−
239.9 to 940.0
4
0.0 to 100.0
0.0 to 210.0
−
20.0 to 120.0
−
40.0 to 250.0
Thermocou-
ple
K
5
−
200 to 1300
−
300 to 2300
−
220 to 1320
−
340 to 2340
6
−
20.0 to 500.0
0.0 to 900.0
−
40.0 to 520.0
−
40.0 to 940.0
J
7
−
100 to 850
−
100 to 1500
−
120 to 870
−
140 to 1540
8
−
20.0 to 400.0
0.0 to 750.0
−
40.0 to 420.0
−
40.0 to 790.0
T
9
−
200 to 400
−
300 to 700
−
220 to 420
−
340 to 740
10
−
199.9 to 400.0
−
199.9 to 700.0
−
219.9 to 420.0
−
239.9 to 740.0
E
11
0 to 600
0 to 1100
−
20 to 620
−
40 to 1140
L
12
−
100 to 850
−
100 to 1500
−
120 to 870
−
140 to 1540
U
13
−
200 to 400
−
300 to 700
−
220 to 420
−
340 to 740
14
−
199.9 to 400.0
−
199.9 to 700.0
−
219.9 to 420.0
−
239.9 to 740.0
N
15
−
200 to 1300
−
300 to 2300
−
220 to 1320
−
340 to 2340
R
16
0 to 1700
0 to 3000
−
20 to 1720
−
40 to 3040
S
17
0 to 1700
0 to 3000
−
20 to 1720
−
40 to 3040
B
18
100 to 1800
300 to 3200
0 to 1820
0 to 3240
W
19
0 to 2300
0 to 4100
−
20 to 2320
−
40 to 4140
PLII
20
0 to 1300
0 to 2300
−
20 to 1320
−
40 to 2340
ES1B
Infrared
Thermosen-
sor
10 to 70
°
C
21
0 to 90
0 to 190
−
20 to 130
−
40 to 270
60 to 120
°
C
22
0 to 120
0 to 240
−
20 to 160
−
40 to 320
115 to 165
°
C 23
0 to 165
0 to 320
−
20 to 205
−
40 to 400
140 to 260
°
C 24
0 to 260
0 to 500
−
20 to 300
−
40 to 580
Anal
og inp
u
ts
Current input
4 to 20 mA
25
Any of the following ranges, by scaling:
−
1999 to 9999
−
199.9 to 999.9
−
19.99 to 99.99
−
1.999 to 9.999
−
5% to 105% of the setting range
0% to 105% for 0 to 20 mA
0 to 20 mA
26
Voltage input
1 to 5 V
27
0 to 5 V
28
0 to 10 V
29
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......