183
Parameter List
Appendix
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
E0 (A0)
Can be
changed
while
stopped.
0000
Decimal Point Position B
H' 00000000: **** (No decimal point) (0)
H' 00000001: ***.* (1)
H' 00000002: **.** (2)
H' 00000003: *.*** (3)
0
---
Common
---
●
0001
Cold Junction Compensation Method
H' 00000000: Externally (0)
H' 00000001: Internally (1)
1
---
Common
●
---
Not used.
0100
Input Type - CH1
H' 00000000: Pt100 (0)
H' 00000001: Pt100 (1)
H' 00000002: Pt100 (2)
H' 00000003: JPt100 (3)
H' 00000004: JPt100 (4)
H' 00000005: K (5)
H' 00000006: K (6)
H' 00000007: J (7)
H' 00000008: J (8)
H' 00000009: T (9)
H' 0000000A: T (10)
H' 0000000B: E (11)
H' 0000000C: L (12)
H' 0000000D: U (13)
H' 0000000E: U (14)
H' 0000000F: N (15)
H' 00000010: R (16)
H' 00000011: S (17)
H' 00000012: B (18)
H' 00000013: W (19)
H' 00000014: PLII (20)
H' 00000015: 10 to 70
°
C (21)
H' 00000016: 60 to 120
°
C (22)
H' 00000017: 115 to 165
°
C (23)
H' 00000018: 140 to 260
°
C (24)
H' 00000019: 4 to 20 mA (25)
H' 0000001A: 0 to 20 mA (26)
H' 0000001B: 1 to 5 V (27)
H' 0000001C: 0 to 5 V (28)
H' 0000001D: 0 to 10 V (29)
5
---
CH
●
---
0101
Temperature Unit - CH1
H' 00000000:
°
C (0)
H' 00000001:
°
F (1)
0
---
CH
●
---
0102
Scaling Upper Limit - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
1000
---
CH
●
---
0103
Scaling Lower Limit - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
0
---
CH
●
---
0104
Decimal Point Position - CH1
H' 00000000: **** (No decimal point) (0)
H' 00000001: ***.* (1)
H' 00000002: **.** (2)
H' 00000003: *.*** (3)
1
---
CH
●
---
Not used.
0200
Input Type - CH2
The rest are the same as channel 1.
···
···
0300
Input Type - CH3
TC4
---
···
···
0400
Input Type - CH4
TC4
---
···
···
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
E1 (A1)
Can be
changed
while
stopped.
Not used.
0101
Control Period 1
H' 00000000 to H' 00000063 (0 to 99)
(0.5 s period when set to 0.)
2
s
IO
●
---
Not used.
0201
Control Period 2
H' 00000000 to H' 00000063 (0 to 99)
(0.5 s period when set to 0.)
2
---
IO
●
---
Not used.
0301
Control Period 3
H' 00000000 to H' 00000063 (0 to 99)
(0.5 s period when set to 0.)
2
---
IO
TC4
---
Not used.
0401
Control Period 4
H' 00000000 to H' 00000063 (0 to 99)
(0.5 s period when set to 0.)
2
---
IO
TC4
---
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......