37
Setup Procedure
Section 3-1
The following table shows the group settings for this example.
The HFU handles all of the operations for gradient temperature control and
2-PID control. The maximum number of enabled channels that can be con-
trolled is selected at the HFU from 4, 8, 16, or 32 channels, and that num-
ber of channels is allocated for the number of groups used.
In this example, the maximum number of enabled channels is three, so the
HFU allocates groups in units of four channels each. The HFU recognizes
the following channels for the Basic Unit.
Variable
type
Address
Parameter
Setting value
F1 (B1)
0000
Number of enabled groups
4
0100
Group 1
Initial Communica-
tions Unit No.
1
0101
Initial Channel
0
0102
Number of Enabled
Channels
3
0103
Control Type
0: Gradient tem-
perature control
0200
Group 2
Initial Communica-
tions Unit No.
2
0201
Initial channel
1
0202
Number of Enabled
Channels
3
0203
Control type
0: Gradient tem-
perature control
0300
Group 3
Initial Communica-
tions Unit No.
4
0301
Initial Channel
0
0302
Number of Enabled
Channels
3
0303
Control Type
0: Gradient tem-
perature control
0400
Group 4
Initial Communica-
tions Unit No.
5
0401
Initial Channel
1
0402
Number of Enabled
Channels
3
0403
Control Type
1: 2-PID control
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......