50
Setting Input Specifications
Section 4-1
4-1
Setting Input Specifications
4-1-1
Input Type
Set the input type to match the type of sensor being used.
List of Input Types
Variable type
Parameter name
Setting range
Default
E0/A0
Input Type
(Channel) 0 to 29
5
Conditions for use
No special conditions
Input type
Specifica-
tion
Set value
Setting range
(°C)
(°F)
Tempera-
ture
input
Platinum
resistance
thermom-
eter
Pt100
0
−
200 to 850
−
300 to 1500
1
−
199.9 to 500.0
−
199.9 to 900.0
2
0.0 to 100.0
0.0 to 210.0
JPt100
3
−
199.9 to 500.0
−
199.9 to 900.0
4
0.0 to 100.0
0.0 to 210.0
Thermo-
couple
inputs
K
5
−
200 to 1300
−
300 to 2300
6
−
20.0 to 500.0
0.0 to 900.0
J
7
−
100 to 850
−
100 to 1500
8
−
20.0 to 400.0
0.0 to 750.0
T
9
−
200 to 400
−
300 to 700
10
−
199.9 to 400.0
−
199.9 to 700.0
E
11
0 to 600
0 to 1100
L
12
−
100 to 850
−
100 to 1500
U
13
−
200 to 400
−
300 to 700
14
−
199.9 to 400.0
−
199.9 to 700.0
N
15
−
200 to 1300
−
300 to 2300
R
16
0 to 1700
0 to 3000
S
17
0 to 1700
0 to 3000
B
18
100 to 1800
300 to 3200
W
19
0 to 2300
0 to 4100
PLII
20
0 to 1300
0 to 2300
ES1B
Infrared
Tempera-
ture
Sensor
10 to 70°C
21
0 to 90
0 to 190
60 to 120°C
22
0 to 120
0 to 240
115 to 165°C
23
0 to 165
0 to 320
140 to 260°C
24
0 to 260
0 to 500
Analog
inputs
Current
input
4 to 20 mA
25
Any one of the following ranges,
by scaling:
−
1999 to 9999
−
199.9 to 999.9
−
19.99 to 99.99
−
1.999 to 9.999
0 to 20 mA
26
Voltage
input
1 to 5 V
27
0 to 5 V
28
0 to 10 V
29
Summary of Contents for EJ1G
Page 3: ...iv ...
Page 17: ...xviii ...
Page 21: ...xxii ...
Page 53: ...32 Unit Configuration Examples Section 2 4 ...
Page 69: ...48 Changing SPs During Operation Section 3 3 ...
Page 81: ...60 Other Functions Section 4 5 ...
Page 145: ...124 Other HFU Functions Section 5 7 ...
Page 167: ...146 Detailed Description of Services Section 6 4 ...
Page 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Page 237: ......