background image

30

Read Address and Write Address

Section 5-6

Percent data is set by registering a setting in a Numeral Display and Input
objects with the integer set to four digits and the decimal to two digits. The
conversion rate/offset for the unit and scale setting is set to a multiplier of
0.01.

5-6

Read Address and Write Address

Even if the tag ITEM is the same for the read address that is read and dis-
played from the PLC to the NS-series PT and the write address that is written
to the PLC from the NS-series PT, the addresses are different.

For example, the following table shows the addresses when Basic PID is
used.

Note

If any values in the receive area (i.e., I/O memory in the CPU Unit) have not
changed, Receive All Blocks in the Loop Control Unit will not receive any data
from the CPU Unit. Therefore, after changing the mode from MAN to AUTO
and then back to MAN mode, such as for Basic PID, and 2-position ON/OFF,
and after changes to the MV set values, the MV value change operation will
not function unless there is a change between the current MAN and previous
MAN mode in the MV write value (receive area value) from the NS-series PT.
In this case, perform an operation to change the MV write value (receive area
value) from the NS-series PT once, and then perform processing. 

The following precaution is required for the Loop Control Unit.
When using an NS project file built with the Face Plate Auto-Builder for NS,
the NS-series PT communicates with the Loop Control Unit via the memory of
the CPU Unit, using the Send/Receive All Blocks block in the Loop Control
Unit. Therefore, compared with accessing the Loop Control Unit using the CX-
Process Tool or CX-Process Monitor software, the communications response
is slower.

10,000 (100%) 

100.00%

11,000 (110%) 

110.00%

Value in device or communications 

Display value

Tag ITEM

Read address

Write address

SP

Determined by the I/O mem-
ory area type, address, and 
bit position of SP in the CSV 
tag file.

Determined by the I/O mem-
ory area type, address, and 
bit position of SP_W in the 
CSV tag file, plus the offset 
(write data).

MV, R/L_SW, A/
M_SW, P, I, D, 
HH_SP, H_SP, L_SP, 
LL_SP, etc.

Determined by the I/O mem-
ory area type, address, and 
bit position of each tag ITEM 
in the CSV tag file.

Determined by the I/O mem-
ory area type, address, and 
bit position of each tag ITEM 
in the CSV tag file, plus the 
offset (write data).

Summary of Contents for Face Plate Auto-Builder for NS 3.1

Page 1: ...Face Plate Auto Builder for NS Ver 3 1 Cat No W418 E1 05 SYSMAC WS02 NSFC1 EV3 OPERATION MANUAL...

Page 2: ...WS02 NSFC1 EV3 Face Plate Auto Builder for NS Ver 3 1 Operation Manual Revised December 2007...

Page 3: ...iv...

Page 4: ...n some OMRON products often means word and is abbreviated Wd in documentation in this sense The abbreviation PLC means Programmable Controller PC is used however in some Program ming Device displays t...

Page 5: ...vi...

Page 6: ...e for Version 3 0 5 1 6 Upgrades Made for Version 3 1 5 SECTION 2 Setup 7 2 1 Installation Method 8 2 2 Uninstalling the Face Plate Auto Builder for NS 11 SECTION 3 Basic Operation Flow 13 3 1 Basic O...

Page 7: ...62 6 8 Indication and Setting Block Model 031 70 6 9 Ratio Setting Block Model 033 73 6 10 High Low Alarm Block Model 111 77 6 11 Timer Block Model 205 79 6 12 Counter Block Model 208 83 6 13 ON OFF V...

Page 8: ...Face Plate Auto Builder for NS WS02 LCTC1 EV3 CX Process Tool CX Process Tool Operation Manual W372 Installation and operation procedures for the CX Process Tool CXONE AL C E CX One FA Integrated Tool...

Page 9: ...Operation Manual W428 Installation and operation procedures for the CX Process Monitor Plus NS CXDC1 V2 CX Designer Ver 2 0 CX Designer User s Manual V088 Operating procedures for the CX Designer NS12...

Page 10: ...S DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE OMRON DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE...

Page 11: ...that the uses listed may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this manual Nuclear...

Page 12: ...onfirm actual specifications of purchased products DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes even when tolerances are shown PERFORMANC...

Page 13: ...xiv...

Page 14: ...ion of the Face Plate Auto Builder for NS You must read this section and understand the information contained before attempting to set up or operate the Face Plate Auto Builder for NS and PLC system 1...

Page 15: ...provide the systems machines and equipment with double safety mechanisms This manual provides information for using the Face Plate Auto Builder for NS Be sure to read this manual before attempting to...

Page 16: ...o Builder for NS 2 1 1 1 Features 2 1 2 System Requirements 3 1 2 1 Computer 3 1 2 2 OS 3 1 3 Application Environment 3 1 3 1 Connection Methods 4 1 4 Upgrades Made for Version 2 0 4 1 5 Upgrades Made...

Page 17: ...Board and Process control CPU Units When using a Loop Control Unit Board and Process control CPU Unit containing NS system version 4 or later up to 100 loops of function block e g PID Control monitor...

Page 18: ...rd CX Process Tool Ver 3 0 or later Using a Loop Control Unit CX Process Tool Ver 2 0 or later Projects built with the Face Plate Auto Builder for NS are used with the follow ing hardware and software...

Page 19: ...n 4 or later System Version Setting for NS Project To Build The output version of the project data after building can be specified NS8 Support Project data can be built for the NS8 EM Multi bank Suppo...

Page 20: ...or Block Model 224 Blended PID Block Model 013 Batch Flowrate Capture Block Model 014 Automatic Comments for Unit and Scaling Settings Comments are automatically entered for automatically allocated un...

Page 21: ...6 Upgrades Made for Version 3 1 Section 1 6...

Page 22: ...7 SECTION 2 Setup 2 1 Installation Method 8 2 1 1 Installation Precautions 8 2 1 2 Installing the Face Plate Auto Builder for NS 8 2 2 Uninstalling the Face Plate Auto Builder for NS 11...

Page 23: ...000 is used be user to use Service Pack 3 or later To check the Service Pack version number from the Start Menu select Settings Control Panel System The System Properties Window will appear Click the...

Page 24: ...cence agreement and click the Next But ton to proceed Step 4 Specify the drive and directory in which the program files will be installed The default setting is C Program Files OMRON CX One FP Auto Bu...

Page 25: ...select the Next Button Step 6 Preparations for executing the installation have been completed Click the Install Button Installation will start from the install program To check or change installation...

Page 26: ...ve Programs from the Control Panel Select Face Plate Auto Builder for NS from the list of applications and click the Change Remove Button Step 2 Click the OK Button The Face Plate Auto Builder for NS...

Page 27: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...

Page 28: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...

Page 29: ...c Operations Specify the CSV tag file compiled using the CX Process Tool to enable the NS Face Plate Screen Project to be automatically built Note Specify a new project for the project to be built aut...

Page 30: ...15 SECTION 4 Operations 4 1 Basic Operation 16 4 2 Merging Projects 21 4 2 1 Merge Using the CX Designer 21 4 2 2 Merging Using the NS Project Merge Tool 22...

Page 31: ...or selecting the CSV tag file Project Name Set the name of the CX Designer project file to be created up to 38 charac ters Output Folder Set the folder that will output the CX Designer project file Cl...

Page 32: ...CX Designer to see if the capacity has been exceeded Screen Number Offset Set the first screen number in the NS series PT Starting from the specified screen number offset screen numbers are assigned...

Page 33: ...stem version 4 and higher and 32 for other versions One is allocated for each registered function block DV scaling settings The total number of freely set values for bank data registered for Segment P...

Page 34: ...NS Version Click this button to display the Version Information Dialog Box for the Face Plate Auto Builder for NS Step 3 Register Host Names When all settings have been completed in step 2 click the...

Page 35: ...e host connection method Any of the following three methods can be set Serial port A serial port B Ethernet CLK Example If the node is connected to serial port A select Serial port A Note The host nam...

Page 36: ...at the same time 2 Select the category in which to paste in the Project Workspace 3 Press the Ctrl V Keys Alternatively right click and select Paste from the pop up menu 4 Specify the number of the fi...

Page 37: ...nfirmation message has been set These settings will be added with numbers changed to not overlap settings already at the copy source Unused communications addresses at the copy destination will be add...

Page 38: ...NS Project Merge Tool The NS Project Merge Tool does not support version 6 6 projects Follow the procedure described in 4 2 1 Merge Using the CX Designer to merge version 6 6 projects The SMART Activ...

Page 39: ...24 Merging Projects Section 4 2...

Page 40: ...Specifications of Created Screens 5 1 Created Screens 26 5 2 Screen Titles 28 5 3 Tuning Screen Realtime Trends 28 5 4 Engineering Units 28 5 5 Percent Data 29 5 6 Read Address and Write Address 30 5...

Page 41: ...llowing screen is a Control Screen when using an NS12 PT Click the Button in the top right corner of the screen to move to the next Control Screen page and click the Button to move to the previous pag...

Page 42: ...0 face plates for system version 4 or later and up to 32 face plates for other system versions are built for the func tion blocks to be converted that are detected when searched from the beginning of...

Page 43: ...ld ing results after returning the communications settings unit and scale setting and data log settings to the default values for creating new projects Specify a new project name in the name for the p...

Page 44: ...207 can be created for system version 4 0 632 if Segment Program 3 blocks are set When building use the Unit Number Offset setting to specify which of the Unit and Scale No data items will be allocat...

Page 45: ...de in the MV write value receive area value from the NS series PT In this case perform an operation to change the MV write value receive area value from the NS series PT once and then perform processi...

Page 46: ...in the macro for the MV Operation Button in the face plate B32766 Used to temporarily read tag ITEM S1 Segment Program 2 Used in the macro for the START STOP Button in the face plate B32767 Used to te...

Page 47: ...pture Used by the macro of the face plate Word Buttons W32712 to W32759 Used to display tag ITEMs Q1 Q2 PR BM BMU SM SMU SP and SPU Used for the Numerical Display and input object of the face plate W3...

Page 48: ...e Plates 59 6 6 2 Tuning Screens 61 6 7 Segment Program 2 Block Model 157 62 6 7 1 Face Plates 63 6 7 2 Tuning Screens 67 6 7 3 Detail Setting Screens 68 6 8 Indication and Setting Block Model 031 70...

Page 49: ...Block Model 013 102 6 17 1 Face Plates 102 6 17 2 Tuning Screens 105 6 18 Batch Flowrate Capture Block Model 014 107 6 18 1 Face Plates 107 6 18 2 Tuning Screens 112 6 19 Segment Program 3 Block Model...

Page 50: ...s set as a label and displayed as a Text object up to 16 characters 3 Tag Comment The tag comment in the CSV tag file is set as a label and displayed as a Text object up to 16 characters 4 Status Disp...

Page 51: ...ut object is used to display the value of tag ITEM PV ITEM 007 in engineering units A Control Flag is set to disable input 9 SP The fixed text SP is displayed as a Text object 10 SP Numerical Value Di...

Page 52: ...and HH are displayed in red and L and H are displayed in light blue color code 219 The maximum value displayed is 11500 115 and the minimum value displayed is 1500 15 The zero point is specified to b...

Page 53: ...60 1 WRITECMEM A M_SW B32761 1 A Control Flag is used to reference the tag ITEM CAS_SET ITEM 024 and if the value is 1 the object is set for no display and to disable input 17 Switch to AUTO Button Th...

Page 54: ...ecrease the value for tag ITEM SP_W ITEM 023 These buttons are created as Word Buttons and are set to increase or decrease the value A Select Shape graphic is used for the Button face display The uppe...

Page 55: ...ject 23 MV Numeral Value Display and Input A Numeral Display and Input object is used to display the value of tag ITEM MV ITEM 089 as percent data When touched a ten key pad is displayed under this fi...

Page 56: ...nput is disabled This function is set using the following macro as a Touch OFF Timing macro for Word Buttons READCMEM B32761 A M_SW 1 if B32761 1 MSGBOX Cannot set MV change 0 RETURN 1 READCMEM W2047...

Page 57: ...on of each object in the face plate is the same as the version for 800 600 screen resolution 6 1 2 Tuning Screens The following screen is a Tuning Screen for Basic PID built using the Face Plate Auto...

Page 58: ...EM using the Before Writing Numeral String macro Button Tag ITEM Color OFF Color ON Label OFF Label ON Write confirmation message Stop block operation command MT_ST ITEM 000 Gray Yellow Operating Oper...

Page 59: ...follows W2047 GETNUMVAL WRITECMEM P I D MH_LMT ML_LMT MV_IDX W2047 1 Parameter Tag ITEM P Proportional band P ITEM 054 I Integral time I ITEM 055 D Differential time D ITEM 056 MH High MV limit MH_LMT...

Page 60: ...lue 6 Switch to Control Screen Button Touch this button to switch to the Control Screen that includes the tag name of the Tuning Screen This button is created as a Command Button 7 Realtime Trend Grap...

Page 61: ...four characters 6 2 Advanced PID Block Model 012 This section describes only the differences between the Advanced PID and Basic PID Block Model 011 For details on the areas not covered here refer to 6...

Page 62: ...ay which is fixed The following values are used in communications between the PLC and NS series PT Data is written to the write address of tag ITEM MRT using the Before Writing Numeral String macro as...

Page 63: ...s between the 2 position ON OFF and Basic PID Block Model 011 For details on the areas not covered here refer to 6 1 Basic PID Block Model 011 6 3 1 Face Plates The face plates are almost the same as...

Page 64: ...hic When the button is touched the tag ITEM A M_SW ITEM 086 is referenced and if the value is 1 a message is displayed indicating that setting is not pos sible and setting is disabled This function is...

Page 65: ...r 2 position ON OFF built with the Face Plate Auto Builder for NS in a 640 480 screen resolution The whole face is built using 458 142 dots The display and operation of each object in the face plate i...

Page 66: ...ch parameter is not provided so up to eight characters can be displayed for the unit character string for 2 position ON OFF instead of the four characters for Basic PID 6 4 Three position ON OFF Block...

Page 67: ...ess set Macros are used to write data The button is displayed as a Select Shape graphic When the buttons are touched tag ITEM A M_SW ITEM 086 is referenced and when the value is 1 a message is display...

Page 68: ...d as an ON OFF Button using a Select Shape of type 1 and switches to display PV error indication characters Control Flag input is dis abled 4 Alarm Status Display MH and ML are not provided with 3 pos...

Page 69: ...st the same as for Basic PID Block Model 011 except for the following differences 1 A setting field for each parameter is not provided 2 AT is not supported 3 MV is not included in the realtime trend...

Page 70: ...of the four characters for Basic PID 6 5 Indication and Operation Block Model 032 This section describes only the differences between the Indication and Setting and Basic PID Block Model 011 For deta...

Page 71: ...isabled 2 Alarm Status Display Indication and Setting does not provide a deviation alarm so there is no dis play 3 Auto Input The fixed characters X1 are displayed as a Text object The numeral display...

Page 72: ...splay color is determined according to the following table The R L_SW is not referenced which is different from Basic PID The label displays MAN in the rough font By setting the following Touch OFF Ti...

Page 73: ...ng Screens The Tuning Screens for Indication and Setting are almost the same as for Basic PID Block Model 011 except that it does not provide PID or AT 1 AT Indication and Setting does not provide an...

Page 74: ...on of each object in the face plate is the same as the version for 800 600 screen resolution 6 6 Indicator Block Model 034 This section describes only the differences between the Indicator and Basic P...

Page 75: ...n MV error indication 2 Alarm Display Indicator does not use the DV MH or ML alarms 3 SP Indicator does not provide an SP 4 Switch to CAS MAN AUTO Button SP Bar Display and SP Change Button The Indica...

Page 76: ...reen resolution 6 6 2 Tuning Screens The Tuning Screens for Indicator are almost the same as for Basic PID Block Model 011 except that it does not provide SP or MV functions and is used as a PV Indica...

Page 77: ...ution The display and operation of each object in the face plate is the same as the version for 800 600 screen resolution Indicator does not provide a setting field for each parameter so up to eight c...

Page 78: ...engineering units the value for tag ITEM X1 ITEM 007 Reference input A Control Flag is set to disable input 4 Y1 Display The fixed string Y1 is displayed as a Text object 5 Y1 Numeral Display A Numera...

Page 79: ...018 is set as the write address and the read address for tag ITEM S4 ITEM 018 is set as display address 1 The label displays ADV in the rough font 11 START Button When touched 1 is set in the write a...

Page 80: ...S2 B32767 1 A Control Flag is used to reference tag ITEM S1 ITEM 013 Run stop com mand If the value is 0 no display input disabled is set 14 PAUSE Button When touched 1 is set in the write address fo...

Page 81: ...displayed with 2 integer digits and 0 digits below the decimal point without scaling the values on the display Other Settings Segment Program 2 does not provide an MV display MV index position SP Chan...

Page 82: ...rite address 1 2 Alarm Setting Parameters Segment Program 2 does not provide alarm settings or parameter settings 3 Realtime Trend Graph Tag ITEM X1 ITEM 007 and tag ITEM Y1 ITEM 008 are displayed as...

Page 83: ...in the build conditions The following screen is the Tuning Screen for Segment Program 2 built using Face Plate Auto Builder for NS in a 640 480 screen resolution The display and operation of each obj...

Page 84: ...tton The button writes the settings made on the screen to the Loop Control Board Unit Note Be sure to check the affect on the controlled system of any changes to be made before actually writing them t...

Page 85: ...nd 4 Backup Button The functions of these buttons are the same as those on the Time Width Out put Value Setting Screen 6 8 Indication and Setting Block Model 031 This section describes only the differ...

Page 86: ...hile in Local mode This button is set as a momentary ON OFF Button using a Simple Rectangle Type 1 and the background color is determined according to the following table The label displays LOCAL in t...

Page 87: ...e whole face is built using 458 142 dots The display and operation of each object in the face plate is the same as the version for 800 600 screen resolution 6 8 2 Tuning Screens The Tuning Screen for...

Page 88: ...of each object in the face plate is the same as the version for 800 600 screen resolution 6 9 Ratio Setting Block Model 033 This section describes only the differences between the Ratio Setting Block...

Page 89: ...023 W32694 1 RETURN 1 When the ten key pad is displayed the tag ITEMs R L_SW and CAS_SET are referenced and if R L_SW is 1 and CAS_SET is 1 a message is displayed indicating that the SP cannot be set...

Page 90: ...equired to operate the Ratio Setting Block can be set on this tuning screen 1 AT The Ratio Setting Block does not provide an AT Button 2 Alarm Setting The Ratio Setting Block does not provide alarm se...

Page 91: ...screen is a Tuning Screen for a Ratio Setting face plate built using the Face Plate Auto Builder for NS in a 640 480 screen resolution ML Low MV limit ML_LMT ITEM077 MV index position MV_IDX 098 Para...

Page 92: ...10 High Low Alarm Block Model 111 This section describes only the differences between the High Low Alarm Block and Basic PID Block Block Model 011 For details on the areas not covered here refer to 6...

Page 93: ...ag ITEM A1 ITEM 009 in engineering units Touch this field to display a ten key pad below it Data is written to the write address of tag ITEM A1 ITEM 009 using the Before Writing Numeral String macro W...

Page 94: ...h Low Alarm face plate does not provide an MV display MV Change Button or MV index position 7 Tuning Screen Button The High Low Alarm face plate does not provide a Tuning Screen Button The following d...

Page 95: ...Numerical Value Display and Input A Numeral Display and Input object is used to display the value of tag ITEM SP ITEM 007 Touch this field to display a ten key pad below it Data is written to the wri...

Page 96: ...ed to set the display color as shown in the following table The button is built as a momentary ON OFF Button using a Simple Rectangle Type 2 The write address is not set and the read address for tag I...

Page 97: ...ad address for tag ITEM S2 ITEM 012 is set as display address 1 The label displays CONT in the rough font The following macro is set as a Touch OFF Timing macro and when touched the fixed value 0 is w...

Page 98: ...agram shows a Timer face plate built using the Face Plate Auto Builder for NS in a 640 480 screen resolution The whole face is built using 458 142 dots The display and operation of each object in the...

Page 99: ...Display and Input A Numeral Display and Input object is used to display the value of tag ITEM SP ITEM 007 Touch this field to display a ten key pad below it Data is written to the write address of ta...

Page 100: ...et and the read address for tag ITEM S1 ITEM 010 is set as display address 1 The label displays START in the rough font The following macro is set as a Touch OFF Timing macro and when touched the fixe...

Page 101: ...n The Counter face plate does not provide a Tuning Screen Button The following diagram shows a Counter face plate built using the Face Plate Auto Builder for NS in a 640 480 screen resolution The whol...

Page 102: ...n using a Simple Rectangle Type 1 to switch the ON OFF labels Control Flag input is disabled 2 Switch to AUTO Button This button switches operation to Auto mode and is displayed in red during Auto mod...

Page 103: ...ON when touched When the button is touched tag ITEM S1 is referenced and if S1 1 the message Could not set will be displayed and the setting will not be accepted Likewise if tag ITEM S4 1 the message...

Page 104: ...setting will not be accepted READCMEM B32760 S1 1 if B32760 1 MSGBOX Could not set OFF Operation 0 RETURN 1 endif READCMEM B32760 S4 1 if B32760 1 MSGBOX Could not set OFF Operation 0 RETURN 1 endif...

Page 105: ...nd single line lamp with the following display col ors A Select Shape graphic is used for the Button face display 9 Closed Limit Switch Input Display ON Display A lamp indicates the status of the clos...

Page 106: ...ilt using the Face Plate Auto Builder for NS in a 640 480 screen resolution The whole face is built using 458 142 dots The display and operation of each object in the face plate is the same as the ver...

Page 107: ...input is disabled 2 CT Input Display A Numeral Display and Input object is used to display the value of tag ITEM X1 ITEM 032 in engineering units Control Flag input is disabled 3 Motor Answer Error D...

Page 108: ...is green maximum value is 11500 115 and minimum value is 1500 15 The bar is set to display the zero point The following diagram shows a Motor Manipulator face plate built using the Face Plate Auto Bu...

Page 109: ...e display color is determined according to the following table The label displays FWD in the rough font By setting the following Touch OFF Timing macro the forward rotation com mand is sent when touch...

Page 110: ...determined according to the following table The label displays OFF in the rough font By setting the following Touch OFF Timing macro the forward operation and reverse operation commands are turned OF...

Page 111: ...ng to the status of tag ITEM S7 The overlapping button s settings are as follows The label displays OFF in the rough font By setting the following Touch OFF Timing macro when tag ITEM S7 1 the message...

Page 112: ...mand is actually sent tag ITEM S6 is turned OFF and then tag ITEM S4 is turned ON READCMEM B32760 S1 1 if B32760 1 MSGBOX Could not set REV Operation 0 RETURN 1 endif READCMEM B32760 S7 1 if B32760 1...

Page 113: ...mp is red when the input is ON The bit lamp is set as a round single line lamp with the following display col ors The label displays REV in the rough font The following diagram shows a Reversible Moto...

Page 114: ...an electric position proportional motor using a target opening value and open close command inputs Combine this function block with other Control blocks such as the PID block to achieve position prop...

Page 115: ...ugh font 5 Open Output Display A lamp indicates the status of the open manipulation output and the lamp is red when the output is ON The bit lamp is set as a round single line lamp with the following...

Page 116: ...mp is red when both inputs are OFF This lamp is created as a momentary ON OFF Button using a Simple Rectan gle Type 3 and the display color is determined according to the following table The label dis...

Page 117: ...es between the Blended PID Block and Basic PID Block Block Model 011 For details on the areas not covered here refer to 6 1 Basic PID Block Model 011 6 17 1 Face Plates This function block performs PI...

Page 118: ...e of tag ITEM MV_ABN determines which status character string is displayed This button is created as an ON OFF Button using a Simple Rectangle Type 2 to switch the ON OFF labels Control Flag input is...

Page 119: ...zero point 7 Y2 Bar Display Displays tag ITEM Y2 using a Level Meter object The meter color is green the maximum value displayed is 11500 115 and the minimum value dis played is 1500 15 The bar is se...

Page 120: ...displayed when a field is touched The following table shows the upper and lower limits of the setting ranges Parameter Referenced tag ITEM Cumulative deviation output DEV_Q 044 Ratio K1 027 Accumulat...

Page 121: ...MV index position 15 00 115 00 Parameter Unit Cumulative deviation output Ratio Accumulated value Same units as Q1 Proportional band Integral time s Differential time s MH High MV limit ML Low MV limi...

Page 122: ...014 This section describes only the differences between the Batch Flowrate Cap ture Block and Basic PID Block Block Model 011 For details on the areas not covered here refer to 6 1 Basic PID Block Mod...

Page 123: ...conversion Control Flag input is disabled 4 SM Value Display A Numeral Display and Input object is used to display the batch accumulated value SM which is calculated by multiplying the batch accumula...

Page 124: ...ngle Type 2 and the display color is determined according to the following table The label displays RESET in the rough font The following macro is set as a Touch OFF Timing macro and when touched the...

Page 125: ...set and the read address for tag ITEM S1 is set as display address 1 The label displays STOP in the rough font The following macro is set as a Touch OFF Timing macro and when touched the fixed value 0...

Page 126: ...ead address for tag ITEM S2 is set as display address 1 The label displays PAUSE in the rough font The following macro is set as a Touch OFF Timing macro and when touched the fixed value 1 is written...

Page 127: ...is displayed when a field is touched The following table shows the upper and lower limits of the setting ranges The following table shows the units that are displayed These units are fixed Parameter...

Page 128: ...dex position W2047 GETNUMVAL WRITECMEM MV_IDX W2047 1 RETURN 1 2 Realtime Trend Graph Tag ITEMs Y1 and MV are displayed in graph format The following table shows the characteristics of each tag ITEM s...

Page 129: ...114 Batch Flowrate Capture Block Model 014 Section 6 18 The display and operation of each object in the face plate is the same as the version for 800 600 screen resolution...

Page 130: ...Manual Cat No W372 6 19 1 Face Plate 1 Status Display Alarm Status Display There is no Alarm Status Display in Segment Program 3 The Status Display indicates the status of X1 input errors Tag ITEM U1...

Page 131: ...t value using a Level Meter object The meter color is green the maximum value displayed is 11500 115 and the minimum value displayed is 1500 15 The bar is set to display the zero point 10 Y1 Bar Tag I...

Page 132: ...ite address is not set and the read address for tag ITEM S1 ITEM 013 is set as display address 1 The label displays START in the rough font The following macro is set as a Touch OFF Timing macro and w...

Page 133: ...or is displayed according to the following table The button is built as a momentary ON OFF Button using a Simple Rectangle Type 2 The write address is not set and the read address for tag ITEM S2 ITEM...

Page 134: ...ontrol Flag is set to disable input Other Settings Segment Program 3 does not provide an MV display MV index position SP Change Button or MV Change Button The following diagram shows the face plate fo...

Page 135: ...m 3 does not provide alarm settings or parameter settings 3 Realtime Trend Graph Tag ITEM X1 ITEM 007 and tag ITEM Y1 ITEM 008 are displayed as graphs Each tag ITEM is drawn using the following graph...

Page 136: ...nated by ITEM 027 AT_PIDNO The bank number is set in the storage destination bank number When the bank number is 0 the current bank the bank num ber designated in the execution step is selected 6 Prog...

Page 137: ...the range of steps that can be written 3 Backup Button This button backs up data during operation This is performed to back up changed settings to the flash memory in the Loop Control Board The backup...

Page 138: ...are displayed and can be set for each step Note Carefully consider the effects that changes will have on equipment before writing any settings Bank Data Setting Screen 1 Read Button This button reads...

Page 139: ...ys banks 16 to 20 21 25 Displays banks 21 to 25 26 30 Displays banks 26 to 30 31 35 Displays banks 31 to 35 36 40 Displays banks 36 to 40 41 45 Displays banks 41 to 45 46 50 Displays banks 46 to 50 51...

Page 140: ...eps 76 to 100 3 and 4 Scale Buttons These buttons are used to change the scale of the output value axis i e scale on the Step Data Graph Display Screen Using percentage data either a 300 0 to 300 0 Sc...

Page 141: ...126 Segment Program 3 Block Model 158 Section 6 19...

Page 142: ...refer to the previous version Revision code Date Revised content 01 February 2003 Original production 02 April 2004 Overall additions and revisions to change information on the Face Plate Auto Builde...

Page 143: ...128 Revision History...

Reviews: