57
Indication and Operation (Block Model 032)
Section 6-5
(R/L_SW is not referenced, which is different from Basic PID.)
The label displays “AUTO” in the rough font.
By setting the following Touch OFF Timing macro, operation will switch to Auto
mode when touched.
$B32761=1;
WRITECMEM ([A/M_SW],$B32761,1) ;
This button is always displayed, without setting a Control Flag to disable the
display and input.
5: Switch to MAN Button
This button switches operation to manual mode and is displayed in red during
manual mode. The button is created as a momentary ON/OFF Button using a
Simple Rectangle (Type 2), and the display color is determined according to
the following table.
(The R/L_SW is not referenced, which is different from Basic PID.)
The label displays “MAN” in the rough font.
By setting the following Touch OFF Timing macro, operation switches to man-
ual mode when touched.
$B32761=0;
WRITECMEM ([A/M_SW],$B32761,1) ;
This button is always displayed, without setting a Control Flag to disable the
display and input.
6: SP Change Button and Switch to CAS Button
Indication and Setting does not provide an SP Change Button or Switch to
CAS Button.
The following diagram shows an Indication and Setting face plate built using
the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
Display color
A/M_SW (ITEM 086)
Yellow
0
Red
1
Red color
A/M_SW (ITEM 086)
Red
0
Yellow
1
Summary of Contents for Face Plate Auto-Builder for NS 3.1
Page 2: ...WS02 NSFC1 EV3 Face Plate Auto Builder for NS Ver 3 1 Operation Manual Revised December 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 21: ...6 Upgrades Made for Version 3 1 Section 1 6...
Page 27: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...
Page 28: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...
Page 39: ...24 Merging Projects Section 4 2...
Page 141: ...126 Segment Program 3 Block Model 158 Section 6 19...
Page 143: ...128 Revision History...