Lit while power is ON.
Lit while the controller is in Run Mode.
Lit when an error has occurred.
Connect the controller to external devices such as a sync sensor and PLC.
Connect cameras.
Connect a DC power supply. Wire the power supply unit independently 

of other devices. After wiring, replace the terminal cover.
Connect the ground wire. Make sure that the controller is grounded with a 

separate ground wire.
Connect a monitor.
Connect an external device such as a personal computer or PLC. 
Connect a track ball, mouse and USB memory. A total of four USB ports are provided and any of them can be 

used. However, when connecting two or more USB memories, do not connect them to adjacent ports. Doing so 

may cause the USB memories to come into contact, resulting in malfunction or damage.

Connect the controller to a personal computer.
A touch pen is stored. (Provided with the LCD integrated type only)

Camera connector

Ethernet connector

Monitor connector (analog RGB)

Power/ground terminal

POWER LED

USB connector

RS-232C/RS-422 connector

I/O connector (control lines, data lines)

 

The following items can be connected to USB ports.       • Commercially available track ball and mouse       • USB memory

• Never insert/remove USB devices during measurement. Doing so may a

ffect measurement time.

RUN LED
ERROR LED

Power Supply Wiring

24VDC


1
2
3

4

5

6 7

8

9

10

11

1
2
3
4
5
6

7

8
9

10

11
12

 The touch pen must be stored so that the pen tip faces to the right when viewed toward the controller. 

 To remove the touch pen, push the left side (handle) of the pen to the rear. The pen

s right side (pen tip) will pop out, so 

hold and remove the pen.

Box type    

FZ4-(H)65□(-10)/FZ4-(H)75□(-10)/FZ4-(H)115□(-10)

I/O Connector

A1
A2
A3
A4

A5
A6
A7
A8
A9

A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21
A22
A23
A24
A25

B1
B2
B3
B4

B5
B6
B7
B8
B9

B10
B11
B12
B13
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25

No.

Wire color Mark (red)

Function

Signal name

No.

COMIN
ENCTRIG_A1 (*2) 
ENCTRIG_B1 (*2) 
STEP1 (*2)/
ENCTRIG_Z1 (*2) 
DSA1 (*2) 
DI1
DI3
DI5
DI7
STGOUT1
(Open)
ERROR
COMOUT1
GATE1 (*2) 
OR1 (*2) 
READY1 (*2) 
COMOUT2
DO1
DO3
DO5
DO7
DO9
DO11
DO13
COMOUT3

Orange
Gray
White
Yellow

Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink

Wire color Mark (blk)

Function

Signal name

Orange
Gray
White
Yellow

Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink

RESET
ENCTRIG_A0
ENCTRIG_B0
STEP0/
ENCTRIG_Z0
DSA0
DI0
DI2
DI4
DI6
STGOUT0
(Open)
RUN/BUSY1 (*2)
BUSY0
GATE0
OR0
READY0
DO0
DO2
DO4
DO6
DO8
DO10
DO12
DO14
DO15

Controller restart
Encoder trigger input(Phase A)
Encoder trigger input(Phase B)

Data send request signal
Command inputs

Strobe trigger output (*1)
(Leave open.)
ON while in Run mode/ON during processing
ON during processing
ON for the set output time
Overall judgment result
ON when image input is allowed
Data output

Common for input signals
Encoder trigger input (Phase A)
Encoder trigger input (Phase B)
Measurement trigger input/
Encoder trigger input (Phase Z)
Data send request signal
Command inputs

Strobe trigger output (*1)
(Leave open.)
ON when there is an error.
Common for control signals
ON for the set output time
Overall judgment result
ON when image input is allowed
Common for output signals
Data output

Common for output signals

Load

Output terminal

COM IN

COM OUT

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
1.1V max.
5 ms max.
0.7 ms max.

*1 ON current/ON voltage

  This refers to the current or voltage values needed to shift from the OFF 

®

 ON state. The ON voltage value is the potential 

difference between each of the input terminals and COM IN.

*2 OFF current/OFF voltage

  This refers to the current or voltage values needed to shift from the ON 

®

 OFF state. The OFF voltage value is the potential 

difference between each of the input terminals and COM IN.

COM IN

Input terminal

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
0.8 V max.
0.1 ms max.
0.1 ms max.

COM IN

Input terminal

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Load

COM OUT

Output terminal

•Handling the output common terminals

COMOUT1: STGOUT0 to 1, RUN/BUSY1, ERROR, BUSY0, OR0 to 1, GATE0 to 1   COMOUT2: READY0 to 1, DO0 to 7   COMOUT3: DO8 to 15

*1 This is a signal that is used when the strobe device is connected to the Controller.

*2 This signal is only available in the Random trigger mode.

 

Internal Specifications

[Input] signals: RESET, DI0 to DI7, DSA0, DSA1

Parallel Interface

[Output] signals: When STGOUT0 and 1 are used, 

connect the COM IN terminal.

Measurement trigger input/Encoder 
trigger input(Phase Z)

NPN I/O type

 FZ4-(H)6□0(-10)/FZ4-(H)7□0(-10)

        

FZ4-(H)11□0(-10)

[Input] signals: STEP0/ENCTRIG_Z0, STEP1/ENCTRIG_Z1, 

ENCTRIG_A0 to 1, ENCTRIG_B0 to 1

[Output] signals: BUSY0, RUN/BUSY1, OR0 to 1, GATE0 to 1, 

ERROR, DO0 to 15, READY0 to 1

I/O Connector

No.

Wire color Mark (red)

Function

Signal name

No.

Wire color Mark (blk)

Function

Signal name

Output terminal

COM IN

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
1.1V max.
5 ms max.
0.7 ms max.

*1 ON current/ON voltage

  This refers to the current or voltage values needed to shift from the OFF 

®

 ON state. The ON voltage value is the potential 

difference between each of the input terminals and COM IN.

*2 OFF current/OFF voltage

  This refers to the current or voltage values needed to shift from the ON 

®

 OFF state. The OFF voltage value is the potential 

difference between each of the input terminals and COM IN.

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
0.8 V max.
0.1 ms max.
0.1 ms max.

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Internal Specifications

[Input] signals: RESET, DI0 to DI7, DSA0, DSA1

Parallel Interface

[Output] signals: When STGOUT0 and 1 are used, 

connect the COM IN terminal.

COM IN

Input terminal

COM OUT

Output terminal

Load

COM IN

Input terminal

 

COM OUT

Load

I/O Connector wiring is the same as NPN I/O type.

PNP I/O type  

 

 FZ4-(H)6□5(-10)/FZ4-(H)7□5(-10)

          

FZ4-(H)11□5(-10)

[Input] signals: STEP0/ENCTRIG_Z0, STEP1/ENCTRIG_Z1, 

ENCTRIG_A0 to 1, ENCTRIG_B0 to 1

[Output] signals: BUSY0, RUN/BUSY1, OR0 to 1, GATE0 to 1, 

ERROR, DO0 to 15, READY0 to 1

Pin numbers will depend on the external device being connected. Refer 

to the manual for the personal computer or PLC being connected.

Pin No.

1
2
3
4
5
6
7
8
9

Signal name

SDB(+)

SD/SDA(-)

RD/RDA(-)

RDB(+)

NC
NC
NC
NC

GND

        Function
For RS-422
For RS-232C/RS-422
For RS-232C/RS-422
For RS-422
Not connected
Not connected
Not connected
Not connected
Signal ground

Connector

Wiring

• 

RS-232C

• 

RS-422

Controller

Use a shielded cable.

The maximum cable length is 15 m.

Use a compatible connector.

• 

Recommended items

RS/CS control cannot be used.

XM3A-0921
XM2S-0911

OMRON Corporation
OMRON Corporation

Signal name

SD
RD

GND

Pin No.

2
3
9

Signal name

SD
RD

GND

Pin No.

*
*
*

External device to be connected

Controller

Use a shielded cable.

Signal name

SDB(+)

SDA(-)
RDA(-)

RDB(+)

Pin No.

1
2
3
4

Pin No.

*
*
*
*

External device to be connected

Signal name

SDA(-)

SDB(+)
RDB(+)

RDA(-)

LCD integrated type

Box type

Plug
Hood

Manufacturer

Model

FZ-VP (2 m, 5 m)

Wire Color

No. mark

Connector

Connect the optional parallel I/O cable (FZ-VP or FZ-VPX).