6

Power Relays 

G7Z

Characteristics

Note: 1. The above values are initial values. 

2. The contact resistance for the Relay (G7Z) was measured with 1 A at 5 VDC using the voltage drop method. 

The contact resistance for the auxiliary contact block (G73Z) was measured with 0.1 A at 5 VDC using the voltage drop method. 

3. The operate time was measured with the rated voltage imposed with any contact bounce ignored at the ambient temperature of 23

°

C. 

4. The insulation resistance was measured with a 1,000-VDC megohmmeter applied to the same places as those used for checking the dielectric strength. 
5. The electrical endurance was measured at an ambient temperature of 23

°

C. 

6. The specifications for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block. 

Approved Standards  

UL Standard: UL508, UL840 (File No. 
E41643) 

Note: Auxiliary contact ratings 

CSA Standard: CSA Certification by 
          : CSA C22.2 No. 14

EN Standard/TÜV Certification: EN 
60947-4-1 (Certification No. R50079155)

Note: Auxiliary contact ratings

Reference Information 

UL 508:

Industrial control devices 

UL 840:

Insulation coordination including clearance 

and creepage distance for electrical devices 

CSA C22.2 No. 14:

Industrial control devices 

EN 60947-4-1:

Contactors 

Classification

Relay (See note 6.) 

Auxiliary contact block

Item

Model

G7Z-4A-

@

Z, G7Z-3A1B-

@

Z, G7Z-2A2B-

@

Z

G73Z-20Z, G73Z-11Z, G73Z-02Z

Contact resistance (See note 2.)

100 m

 max.

Operating time (See note 3.) 

50 ms max.

Release time (See note 3.) 

50 ms max.

Maximum operating 
frequency

Mechanical

1,800 operations/h

Rated load

1,200 operations/h

Insulation resistance (See note 4.) 

1,000 M

 min.

Dielectric strength

Between coil and contacts 

4,000 VAC, 50/60 Hz for 1 min 

---

Between contacts of different polarity 

4,000 VAC, 50/60 Hz for 1 min 

Between contacts of the same polarity  2,000 VAC, 50/60 Hz for 1 min 

Impulse withstand 
voltage 

Between coil and contacts 

10 kV, 1.2 

×

 50 µs

---

Between contacts of different polarity 

10 kV, 1.2 

×

 50 µs

Between contacts of the same polarity  4.5 kV, 1.2 

×

 50 µs

Vibration resistance

Destruction

10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) 

Malfunction

NO: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) 
NC: 10 to 32 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) 

Shock resistance

Destruction

Screw mounting: 800 m/s

2

, DIN Track mounting: 500 m/s

2

 

Malfunction

NO: 100 m/s

2

 

NO: 25 m/s

2

  

Endurance

Mechanical

1,000,000 operations min. (at 1,800 operations/h, contact no load) 

Electrical (See note 5.)

AC resistive load: 80,000 operations 
AC inductive load: 80,000 operations 
DC resistive load: 100,000 operations 
(at 1,200 operations/h, rated load)

Failure rate P value (reference value)  

2 A at 24 VDC

1 mA at 5 VDC

Ambient operating temperature

25 to 60

°

C (with no icing or condensation) 

Ambient operating humidity

5% to 85% 

Weight

Approx. 330 g

Model

Coil 

ratings

Contact ratings

Number of 

test 

operations

G7Z

12, 24 VDC NO 

contact 

40 A, 480 VAC, 60 Hz 
(Resistive)

80,000

5 A, 120 VDC (Resistive)

100,000

22 A, 480 VAC, 60 Hz 
(General Use)

100,000

D300* (1-A current applied)

---

NC 
contact

25 A, 480 VAC, 60 Hz 
(Resistive)
5 A, 120 VDC (Resistive)
10 A, 480 VAC, 60 Hz 
(General Use)

100,000

D300* (1-A current applied)

---

Model

Contact ratings

G73Z

NO contact 

D300 (1-A current applied)

NC contact

Model

Coil ratings

Contact ratings

G7Z

12, 24 VDC

NO contact  AC-1: 40 A, 440 V, 50/60 Hz

AC-3: 16 A, 440 V, 50/60 Hz
DC-1: 5 A, 110 V
*AC15: 0.5 A, 440 V, 50/60 Hz
*DC13: 0.5 A, 110 V

NC contact AC-1: 25 A, 440 V, 50/60 Hz

DC-1: 5 A, 110 V
*AC15: 0.5 A, 440 V, 50/60 Hz
*DC13: 0.5 A, 110 V

G73Z

---

NO contact  AC15: 0.5 A, 440 V , 50/60 Hz

DC13: 0.5 A, 110 V

NC contact

Summary of Contents for G7Z

Page 1: ...rying and Switching 40 A at 440 VAC Compact High Insulation High Capacity Low Noise Safety Function RoHS Compliant Simple Mounting Low Power Consumption IEC AC1 40 A rating 4 pole power fully applied...

Page 2: ...mple General Safety Circuit G9SA 301 24 V AC DC two limit switch input channels with manual reset Compact Size Safety Function with Mirror Contacts Low Noise and Low Power Consumption DIN Track Mounta...

Page 3: ...T NO 11 SPST NO SPST NC 02 DPST NC 3 Contact Mechanism of Auxiliary Contacts Z Bifurcated crossbar contact Auxiliary Contact Block 1 Contact Configuration of Auxiliary Contacts 20 DPST NO 11 SPST NO S...

Page 4: ...T NO SPST NC 12 24 VDC G7Z 2A2B 11Z DPST NC 12 24 VDC G7Z 2A2B 02Z Contact configuration Model DPST NO G73Z 20Z SPST NO SPST NC G73Z 11Z DPST NC G73Z 02Z Item Rated current Coil resistance Must operat...

Page 5: ...Hz for 1 min Between contacts of different polarity 4 000 VAC 50 60 Hz for 1 min Between contacts of the same polarity 2 000 VAC 50 60 Hz for 1 min Impulse withstand voltage Between coil and contacts...

Page 6: ...ity Note The coil has no polarity G7Z 2A2B 20Z G7Z 2A2B 11Z G7Z 2A2B 02Z Note The coil has no polarity Note The coil has no polarity Note The coil has no polarity 53 54 63 64 7 5 3 1 A1 8 6 4 2 A2 53...

Page 7: ...ers and servo drivers for public and industrial use Power supplies applied to uninterruptible power supplies plus single and three phase power supply switching for public and industrial use Single and...

Page 8: ...two or more Relays are mounted in a row The auxiliary contact block G73Z can be mounted on the Relay Mounting and Removal Mounting Insert the tab on the auxiliary contact block into the groove on the...

Page 9: ...tus feedback Operating Coil Internal Connections of Coils DC Coil If a transistor drives the G7Z check the leakage current and connect a bleeder resistor if necessary The must operate voltage is the m...

Page 10: ...Power Relays G7Z 11...

Page 11: ...DAMAGES LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED ON CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY In no event shall the responsibility o...

Reviews: