2 - 7
CompoNet Gateway Unit for CC-Link Operation Manual
2-
2 Co
mpo
nen
t Name
s
a
nd Fu
ncti
ons
2
CC-Link Communications Section
z
CC-Link Communications Indicators
Status
Displayed
contents
Description
Error
Initialization error
Error code
The error code is shown on the display in hexadecimal.
Communications error
The error
code, node
type, and
applicable
node address
are displayed
in order.
Error code (2-digit hexadecimal)
→
Slave Unit type
→
Node address (3-digit decimal: 100s digit is indicated with 1 bit dot) are
displayed in order (for each error cause).
Note: Error codes are different for inputs and outputs.
Example
Error code
Slave Unit type
Display
Display
appearance
Display
Display
appearance
Meaning
Communications
error
d9
i
IN
o
OUT
bi
Bit Input
Unit
bo
Bit Output
Unit
r
Repeater
Unit
Node address
duplication
d0
Same as above.
Verification error:
Slave Unit
missing.
d5
Same as above.
Verification error:
Unregistered
Slave Unit
d6
Same as above.
Operating error
Note: “Operating errors”
are all errors
except for com-
munications
errors that occur
during Unit oper-
ation.
Error code
The error code is shown on the display in 2-digit hexadecimal.
Example
Error code
---
Display
Display
appearance
Illegal
registration table
E8
---
Indicator
Status
Status definition
L RUN
Lit green
CC-Link data links are active.
Not lit
Communications for CC-Link data links have been interrupted.
L ERR
Lit red
•
A CC-Link data link communications error has occurred or the baud rate of the
Gateway Unit is different from the baud rate of the CC-Link Master Unit.
•
The station number switch is set out of range.
Flashing red
The setting of the baud rate DIP switch or station number switch was changed while
power was ON.
SD
Lit yellow
Data is being transmitted normally.
Not lit
No data is being transmitted.
RD
Lit yellow
Data is being received normally.
Not lit
No data is being received.
Summary of Contents for GQ-CRM21