Mode Switch
This switch sets the communications mode number for the Gateway Unit. It is set to between 0 and 6 on
a decimal rotary switch. The expanded cyclic setting (a network parameter set with the GX-Developer)
in the station information must be set according to the communications mode as shown below.
Note: Do not set communications mode numbers 7 to 9. They are reserved.
Mode
number
Name
Connectable node
addresses
Control points
CC-Link version and
expanded cyclic
setting
0
(default)
Communications
mode 0
Word Slave Unit: IN0 to
IN63 and OUT0 to OUT63
Bit Slave Unit: IN0 to IN127
and OUT0 to OUT127
Word Slave Unit: 1,024
inputs and 1,024 outputs
Bit Slave Unit: 256 inputs
and 256 outputs
Version 2, octuple
(default)
1
Communications
mode 1
Word Slave Unit: IN0 to
IN31 and OUT0 to OUT31
Bit Slave Unit: IN0 to IN95
and OUT0 to OUT95
Word Slave Unit: 512
inputs and 512 outputs
Bit Slave Unit: 192 inputs
and 192 outputs
Version 2, quadruple
2
Communications
mode 2
Word Slave Unit: IN0 to
IN15 and OUT0 to OUT15
Bit Slave Unit: IN0 to IN47
and OUT0 to OUT47
Word Slave Unit: 256
inputs and 256 outputs
Bit Slave Unit: 96 inputs
and 96 outputs
Version 2, double
3
Communications
mode 3
Word Slave Unit: IN0 to IN7
and OUT0 to OUT7
Bit Slave Unit: IN0 to IN15
and OUT0 to OUT15
Word Slave Unit: 128
inputs and 128 outputs
Bit Slave Unit: 32 inputs
32 outputs
Version 1
4
Communications
mode 4
Word Slave Unit: IN0 to
IN63 and OUT0 to OUT63
Bit Slave Unit: IN0 to IN127
and OUT0 to OUT127
Word Slave Unit: 1,024
inputs and 1,024 outputs
Bit Slave Unit: 256 inputs
and 256 outputs
Version 2, quadruple
5
Communications
mode 5
Word Slave Unit: IN0 to
IN31 and OUT0 to OUT31
Bit Slave Unit: IN0 to IN95
and OUT0 to OUT95
Word Slave Unit: 512
inputs and 512 outputs
Bit Slave Unit: 192 inputs
and 192 outputs
Version 2, double
6
Communications
mode 6
Word Slave Unit: IN0 to
IN15 and OUT0 to OUT15
Bit Slave Unit: IN0 to IN47
and OUT0 to OUT47
Word Slave Unit: 256
inputs and 256 outputs
Bit Slave Unit: 96 inputs
and 96 outputs
Version 1
7 to 9
Reserved
---
---
---
Summary of Contents for GQ-CRM21
Page 1: ...OPERATION MANUAL Cat No W489 E1 01 GQ CRM21 CompoNet Gateway Unit for CC Link ...
Page 21: ...1 Overview 1 1 Overview 1 1 ...
Page 25: ...2 Description of Gateway Unit 2 1 Specifications 2 1 2 2 Component Names and Functions 2 4 ...
Page 38: ...2 13 CompoNet Gateway Unit for CC Link Operation Manual 2 2 Component Names and Functions 2 ...
Page 102: ......