A3 - 3
A3 Appendix GRT1-ECT Specifications
GRT1-series EtherCAT Communication Unit - Operation Manual
A3-1
S
p
ecifica
tion
s GRT1-
E
CT
A
A3-1-
4 Supporte
d SmartSlice I/O
Unit
s
The GRT1-ECT supports a sub-set of the available SmartSlice I/O Units. The table below lists all
models supported.
1)
Supported from GRT1-ECT version 2.1
A3-1-4 Supported SmartSlice I/O Units
Model
Function
Specification
GRT1-ID4
4 NPN inputs
24 VDC, 6 mA, 3-wire connection
GRT1-ID4-1
4 PNP inputs
24 VDC, 6 mA, 3-wire connection
GRT1-ID8
8 NPN inputs
24 VDC, 4 mA, 1-wire conn 4xG
GRT1-ID8-1
8 PNP inputs
24 VDC, 4 mA, 1-wire conn 4xV
GRT1-OD4
4 NPN outputs
24 VDC, 500 mA, 2-wire connection
GRT1-OD4-1
4 PNP outputs
24 VDC, 500 mA, 2-wire connection
GRT1-OD4G-1
4 PNP outputs
with shortcircuit protection
24 VDC, 500 mA, 3-wire connection
GRT1-OD4G-3
4 PNP outputs
with shortcircuit protection
from 4 x 2.0 A at 30°C to 4 x 1.0 A at 55°C
GRT1-OD8
8 NPN outputs
24 VDC, 500 mA, 1-wire conn 4xV
GRT1-OD8-1
8 PNP outputs
24 VDC, 500 mA, 1-wire conn 4xG
GRT1-OD8G-1
8 PNP outputs
with shortcircuit protection
24 VDC, 500 mA, 1-wire conn 4xG
GRT1-ROS2
2 relay outputs
240 VAC, 2A, normally-open contacts
GRT1-AD2
2 analog inputs, current/voltage
10 V, 0-10 V, 0-5 V, 1-5 V, 0-20 mA, 4-20 mA
GRT1-DA2V
2 analog outputs, voltage
10 V, 0-10 V, 0-5 V, 1-5 V
GRT1-DA2C
2 analog outputs, current
0-20 mA, 4-20 mA
GRT1-IA4-1
Four-point AC Input Unit
100 to 120 VAC 50/60 Hz
GRT1-IA4-2
Four-point AC Input Unit
200 to 240 VAC 50/60 Hz
GRT1-TS2P
Two-point Temperature
Input Unit
Resistance thermometer input, Input type:
PT100 (
−
200 to 850°C) or PT100 (
−
200 to 200°C)
GRT1-TS2PK
Two-point Temperature
Input Unit
Resistance thermometer input, Input type:
PT1000 (
−
200 to 850°C) or PT1000 (
−
200 to 200°C)
GRT1-TS2T
Two-point Temperature
Input Unit
Thermocouple input, Input type: R, S, K J, T, E, B, N, L,
U, W, or PL2
GRT1-CT1
1)
60 kHz Counter unit, NPN
A+B encoder 1 Z/control input + 1 output
(NPN-type)
GRT1-CT1-1
1)
60 kHz Counter unit, PNP
A+B encoder 1 Z/control input + 1 output
(PNP-type)
GRT1-CP1-L
1)
100 kHz Counter / Positioner unit
A+B+Z encoder inputs (line driver or 24 V selectable) +
1 control input + 2 outputs (PNP-type)
GRT1-END
End plate
One unit required per bus interface
GRT1-PD2
I/O power feed Unit, separates power supply between groups of I/O units
GRT1-PD2G
I/O power feed Unit with electronic overload protection, separates power supply between
groups of I/O units
GRT1-PD8
I/O power feed and distribution Unit, separates power supply between groups of I/O units, 8xV
+ 4xG
GRT1-PD8-1
I/O power feed and distribution Unit, separates power supply between groups of I/O units, 8xV
+ 4xG
GRT1-PC8
I/O power connection Unit, 8xV + 4xG
GRT1-PC8-1
I/O power connection Unit, 4xV + 8xG
GRT1-TBR
Turnback Unit, right-hand side
GRT1-TBL
Turnback Unit, left-hand side
GCN2-100
Turnback cable, one meter
Summary of Contents for GRT1-ECT SmartSlice
Page 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Page 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...