A4 Appendix Object Dictionary
A4 - 14
GRT1-series EtherCAT Communication Unit - Operation Manual
•
When a Unit does not participate in I/O data exchange, its Participation index will go FALSE.
•
When a Unit withdraws from I/O communication during replacement, the corresponding SmartSlice
I/O Unit Communication Withdrawn index will go TRUE and the EtherCAT Communication Unit’s TS
indicator will flash red.
•
The GRT1-ECT status flags give the status of the connection between the GRT1-ECT and the
SmartSlice I/O Units, and the status of the SmartSlice I/O Units.
F060 hex
SmartSlice I/O Unit participation list
Sub-index 0: Number of SmartSlice I/O Units
Range:
−
Unit:
−
Default: hh
Attribute:
−
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Sub-index 1: Participation state of SmartSlice unit 1
Range: 0 to 1
Unit:
−
Default:
−
Attribute:
−
Size: 1 bit (BOOL)
Access: RO
PDO map: Not possible
Sub-index ...
Range: 0 to 1
Unit:
−
Default:
−
Attribute:
−
Size: 1 bit (BOOL)
Access: RO
PDO map: Not possible
Sub-index 1: Participation state of SmartSlice Unit hh
Range: 0 to 1
Unit:
−
Default:
−
Attribute:
−
Size: 1 bit (BOOL)
Access: RO
PDO map: Not possible
F061 hex
SmartSlice I/O unit withdrawal list
Sub-index 0: Number of SmartSlice I/O Units
Range:
−
Unit:
−
Default: 01 hex
Attribute:
−
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Sub-index 1: Withdrawal state of SmartSlice unit 1
Range: 0 to 1
Unit:
−
Default:
−
Attribute:
−
Size: 1 bit (BOOL)
Access: RO
PDO map: Not possible
Sub-index ...
Range: 0 to 1
Unit:
−
Default:
−
Attribute:
−
Size: 1 bit (BOOL)
Access: RO
PDO map: Not possible
Sub-index 1: Withdrawal state of SmartSlice Unit hh
Range: 0 to 1
Unit:
−
Default:
−
Attribute:
−
Size: 1 bit (BOOL)
Access: RO
PDO map: Not possible
F100 hex
Communication Unit status
Sub-index 0: Number of objects
Range:
−
Unit:
−
Default: 01 hex
Attribute:
−
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Sub-index 1: Communication Status
Range: 0000 hex to FFFF hex
Unit:
−
Default:
−
Attribute:
−
Size: 2 bytes (U16)
Access: RO
PDO map: Possible
Bit
Name
Contents
0
SmartSlice I/O Bus
Communication Error
Monitors the status of SmartSlice I/O communication
1
-
Reserved
2
SmartSlice I/O Unit Warning
0: Normal
1: Error detected
Indicates a minor SmartSlice I/O Unit error.
This flag goes ON when there is an error in any one of
the connected SmartSlice I/OUnits.
3
-
Reserved
4
SmartSlice I/O Unit Alarm
0: Normal
1: Error detected
Indicates a major SmartSlice I/O Unit error.
This flag goes ON when there is an error in one of the
connected SmartSlice I/O Units.
5-11
-
Reserved
12
Unit Maintenance
0: Normal
1: Error (monitor value reached)
Monitors the operating time threshold that is set with
the Unit power ON time monitor function
Summary of Contents for GRT1-ECT SmartSlice
Page 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Page 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...