4 GRT1-ECT Details
4 - 4
GRT1-series EtherCAT Communication Unit - Operation Manual
Reference
The timing of each flashing state of indicator is as follows.
Indicates the status of the SmartSlice I/O system.
[TS] indicator
Color
State
Contents
N/A
OFF
No power supply
Communication with SmartSlice I/O Unit has not started
Overcurrent detected
Green
Flashing
(every second)
SmartSlice I/O Unit added to the system
Flashing
(every 0.5 second)
Backup/Restore function operating:
Restoring settings to SmartSlice I/O Unit, backup function
operating
Downloading SmartSlice I/O Unit settings
ON
Communication with SmartSlice I/O Unit established
Red
Flashing
Non-fatal communication error occurred.
Communication timeout
Verification error occurred with registered table
Different model unit detected after SmartSlice I/O Unit
replacement
ON
Fatal communication error occurred.
Lit for 2 s
Failure occurred while restoring settings to I/O unit or
downloading I/O unit settings
on
off
on
off
on
off
on
off
Flickering
Blinking
Single flash
Double flash
50 ms
200 ms 200 ms
200 ms
200 ms
1000 ms
200 ms 200 ms 200 ms
1000 ms
Summary of Contents for GRT1-ECT SmartSlice
Page 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Page 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...