7 - 15
7 GRT1-ECT Installation
GX-series EtherCAT Slave Unit User’s Manual
7-3 Inst
allin
g the Power Sup
p
lies
7
7-3
-5 Wirin
g Methods
Supplying Power to the Units
Connect the power supply wires (24 VDC) to the EtherCAT Communication Unit’s screwless
clamping power supply terminals. If pin terminals are used on the wire ends, the pin terminals can
just be inserted to wire the power.
Precautions for Correct Use
The GRT1-TBL Left Turnback Unit has the same screwless clamping power supply terminals as
the EtherCAT Communication Unit. These terminals are wired in the same way, by inserting the
power supply wires.
Supplying I/O Power
The power supply for I/O devices is supplied through the EtherCAT Communication Unit’s screwless
clamping power supply terminals. If pin terminals are used on the wire ends, the pin terminals can
be inserted to wire the power.
Precautions for Correct Use
The GRT1-TBL Left Turnback Unit and GRT1-PD2 I/O Power Supply Unit have the same
screwless clamping power supply terminals. These terminals are wired in the same way as the
EtherCAT Communication Unit’s terminals, by inserting the power supply wires.
7-3-5
Wiring Methods
These terminals supply power to both
the EtherCAT Communication Unit's
internal circuits and the connected
SmartSlice I/O Units' internal circuits.
Holes for wires
(pin terminals)
Release button
Press the release button with
a screwdriver and pull out the
wire (pin terminal).
24 VDC
These terminals supply power to the
external I/O devices connected to the
SmartSlice I/O Units.
Holes for wires
(pin terminals)
Release button
Press the release button with
a screwdriver and pull out the
wire (pin terminal).
24 VDC
Summary of Contents for GRT1-ECT SmartSlice
Page 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Page 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...