Ratings
Rated supply voltage
100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range
85% to 110% of rated supply voltage
Power reset
Minimum power-opening time: 0.5 s
Power consumption
100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs
Relay output: 5 A at 250 VAC/30 VDC, resistive load (cos
φ
= 1)
Characteristics
Accuracy of operating
time
±
0.2% FS max.
Setting error
±
5% FS
±
50 ms max.
Accuracy of Star-delta
transfer time
±
25% FS + 5 ms max.
Reset voltage
10 % max. of rated voltage
Influence of voltage
±
0.2% FS max.
Influence of
temperature
±
1% FS max.
Insulation resistance
100 M
Ω
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying
metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity
±
1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1
µ
s, 1-ns
rise)
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance
Destruction:10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s
2
three times each in six directions
Malfunction: 294 m/s
2
three times each in six directions
Ambient temperature
Operating:–10
°
C to 55
°
C (with no icing)
Storage: –25
°
C to 65
°
C (with no icing)
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical:20 million operations min. (under no load at 1,800 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
EMC
(EMI)
EN50081-2
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
(EMS)
EN50082-2
Immunity ESD:
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves:
ENV50140: 10 V/m (80 MHz to 1 GHz)
(level 3)
Immunity RF-interference from Pulse-modulated Radio Waves:
ENV50204: 10 V/m (900
±
5 MHz) (level 3)
Immunity Conducted Disturbance: ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge:
EN61000-4-5:
1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color
Light Gray (Munsell 5Y7/1)
Enclosure ratings
IP40 (panel surface)
Weight
H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g