H5BR

H5BR

14

Installation

Terminal Arrangement

6

5

3

1

2

4

7

Gate input

12 V

Reset input

Start signal input

Batch count reset
input

Key protect input

OUT

100 to 240 VAC/24 VAC

12 to 24 VDC

15

16

17

18

H5BR-B (Standard)
Contact and
Transistor outputs

OUT

8

9 10 11

13

12

14

Batch

External
power
supply

(-)

(+)

Common
0 V

(-)

(+)

Unused

Unused

Note:

Do not connect unused terminals.

Connections

The inputs of the H5BR are no-voltage (short circuit or open) inputs.

No-voltage Input Signal Levels

No-contact
input

Contact
input

1. High level
Transistor ON
Residual voltage: 2 V max.
Impedence when ON: 1 k

"

max.

2. Low level
Transistor OFF
Impedence when OFF: 100 k

"

min.

Use contacts which can adequate-
ly switch 2 mA at 5 V

No-contact Input
(NPN Transistor)

Contact Input

No-contact Input

Sensor

Timer

High: transistor ON

Timer

High: contact ON

High: transistor ON

Sensor

Timer

12 VDC

Start signal,
reset, etc.

Input use 0 V

Start signal,
reset, etc.

Input use 0 V

12 VDC

+V

(30 V max.)

Input use 0 V

Start signal,
reset, etc.

Summary of Contents for H5BR Series

Page 1: ...forms to EMC standards Six language instruction manual provided RC Ordering Information Functions 9 field selectable Contact type One SPDT relay and two NPN open collector transfor output Terminal form 18 terminal screws on rear of case Part number H5BR B Supply voltage AC 24 100 to 240 V 50 60 Hz DC 12 to 24 V Note Specify both the model and control power supply when ordering Model Legend H5BR Ty...

Page 2: ...s Elapsed time UP remaining time DOWN Output modes A A 1 A 2 A 3 b b 1 d E F Reset system Power reset except A 3 b 1 and F modes External manual automatic resets internal according to A 1 b b 1 d and E mode operation Batch counting function Yes Sensor power supply 12 VDC Input signals Start reset gate batch count reset key protect inputs Input method No voltage input Via opening and closing of con...

Page 3: ...luding temperature and voltage effects Power start 0 01 0 05 s max Control signal start 0 005 0 03 s max rate for set value Insulation resistance 100 M min at 500 VDC between current carrying terminal and exposed non current carrying metal parts and between non continuous contacts Dielectric strength 2 000 VAC 50 60 Hz for 1 min between current carrying terminal and exposed non current carrying me...

Page 4: ...ches to the present value display Operation key 15 Batch key Switches to the batch display 16 Mode key Switches from run mode to setting mode Changes items in the setting mode 17 Reset key Resets timing and outputs Factory Settings The following table shows the timer settings when it is shipped Please change the settings as necessary to suit the system before operation Settings and the display rec...

Page 5: ...s are not accepted while reset input is ON Reset indicator lit while reset input is ON Gate Inhibits timer operation Batch count reset Resets batch count to zero and batch output turns OFF on leading edge Batch count signals are not accepted while batch count reset is ON Key protect Makes keys inoperative according to key protect level Key protected indicator lit while key protect input is ON Effe...

Page 6: ...etting mode Press the DISPLAY key Press the BATCH key Press the DISPLAY key Press the MODE key Press the MODE key Press the MODE key Press the MODE key Press the MODE key Press the MODE key Press the MODE key Note 1 Set values are changed using the increment keys 1 to 4 2 The large arrows indicate the parameter displayed first when the mode is changed with the MODE or DISPLAY key ...

Page 7: ...utput time Determines the duration of the control output Will be displayed when the output mode is A A 1 A 2 A 3 b or b 1 Will not be displayed when the output mode is d E or F Use keys 1 to 3 to change the value Key1 adjusts the first digit 0 1 s digit Key2 adjusts the second digit 1 s digit Key3 adjusts the third digit 10 s digit Key4 selects either hold output or one shot output 0 1 2 8 9 hold ...

Page 8: ...e Nonsignificant zeros are normally not shown on the set value display Note Read Changing Set Values in the Precautions section pg 15 before changing the Timer set value during operation Changing the Batch Count Set Value 1 Press the BATCH key to switch from the present value display to the batch count display 2 Change the set value when the Timer is set to the batch count display Nonsignificant z...

Page 9: ...s enabled Settings changed in the setting mode are not effective until run mode is entered As the operating conditions will change in this case always reset operation with the RESET key or a reset input 2 Press the MODE key to scroll successively through the items that can be set 3 Changing the selected item Press the MODE key until the desired item appears Change the item setting by pressing keys...

Page 10: ...r for a programmable one shot time period Output mode A 2 Power ON delay 1 Timer resets when power comes on t Power Start signal Gate Reset Control output Set value Timing diagram UP DOWN 0 0 Set value Timing begins when power is applied Start signals act as a gate input causing the present value to The control output will be energized when the present value equals the preset time The output can b...

Page 11: ...ated until a reset input is applied or power is interrupted Output mode b 1 Repeat cycle 2 Timer does not reset when power comes on Power Start signal Gate Reset Control output Set value Timing diagram UP DOWN 0 0 Set value The OFF ON cycle is initiated at the leading edge of the start signal The output relay will be OFF for the preset time then ON for the preset time The cycle will be repeated un...

Page 12: ...e output is sustained until power is interrupted or a reset signal applied Batch Counter Operation Batch count reset Batch output Batch count set value Batch count pres ent value 0 The batch count output holds until reset by the batch count reset The present value of the batch count advances continuously 1 The batch count present value remains at 0 while the batch count reset is ON 2 When the batc...

Page 13: ...less otherwise indicated Flush Mounting H5BR M3 5 terminal screw effective length 6 mm 7 panel thickness Flush Mounting Adaptor Panel Cutouts Panel cutouts are as shown at right according to DIN43700 Panel 72 72 6 100 67 6 100 6 100 min 82 min 68 0 7 0 68 0 7 0 ...

Page 14: ... the H5BR are no voltage short circuit or open inputs No voltage Input Signal Levels No contact input Contact input 1 High level Transistor ON Residual voltage 2 V max Impedence when ON 1 k max 2 Low level Transistor OFF Impedence when OFF 100 k min Use contacts which can adequate ly switch 2 mA at 5 V No contact Input NPN Transistor Contact Input No contact Input Sensor Timer High transistor ON T...

Page 15: ...SET key Display Error Output status Correction Setting e1 CPU OFF Press RESET key No change e2 Memory batch count to 0 Set at the factory Changing Set Values The Timer set value can be changed while the timer is operating so a high value can be set temporarily to inactivate the timer or a low value can be set to activate the timer more quickly If the set value is changed accidentally during operat...

Reviews: