H7CZ
14
Input/Output Mode Settings
Input mode
Operation after count
completion
UP
DOWN
Output
mode
setting
N
The outputs and present
value display are held
until reset is input.
F
The present value
display continues to
increase/decrease.
The outputs are held until
reset is input.
C
As soon as the count
reaches SV, the present
value display returns to
the reset start status.
The present value display
does not show the
present value upon count-
up.
The outputs repeat one-
shot operation.
R
The present value
display returns to the
reset start status after
the one-shot output time.
The outputs repeat one-
shot operation.
K-1
The present value
display continues to
increase/decrease.
Self-holding
output
One-shot
(The one-shot output time can be
set in the range 0.01 to 99.99s.)
Reset
OUT
999999
Set value
0
999999
0
Reset
OUT
Set value
999999
0
Reset
OUT
Set value
999999
0
Reset
OUT
Set value
999999
0
Reset
OUT
Set value