background image

K2CU

K2CU

2

Specifications

 Ratings

Item

K2CU-F

K2CU-P

Control supply voltage

100, 110, 200, 220 VAC

100/200, 110/220 VAC

Rated frequency

50/60 Hz

Carry current

1.25 times as large as each model’s
maximum operating current

2.5 A for K2CU-P0.5A-A/-B;
5 A

Operating voltage range

85% to 110% of control supply voltage

Voltage fluctuation compensation
range

85% to 110% of control supply voltage

85% to 110% of control supply voltage
(applicable only on models with voltage
fluctuation compensation)

Operating current

4 to 10 A, 8 to 20 A, 16 to 40 A, 32 to 80 A
(continuously variable)

0.25 to 0.5 A, 0.5 to 1 A, 1 to 2 A, 2 to 4 A
(continuously variable)

Releasing current

105% max. of operating current

110% max. of operating current

Operate time

0.5 s max. (when current changes from 150% to 0%)

Gate input voltage range (for
models with gate input terminals)

5 to 30 VDC

---

Control output

2 A at 220 VAC, SPDT (cos

φ

 = 0.4)

Power consumption

Input: 0.5 VA max.
Power supply: 5 VA max.

Input: 1 VA max.
Power supply: 4 VA max.

 Characteristics

Setting accuracy

±

7% max.

Repeat accuracy

±

3% max.

Influence of temperature

±

10% max. (at 20

°

C

±

30

°

C)

Influence of voltage

Models without voltage fluctuation compensation:

±

3% max. of the value measured at the control supply voltage, on condition that the voltage

fluctuation is 85% to 110% of the control supply voltage
Models with voltage fluctuation compensation:

±

5% max. of the logical value, on condition that the voltage fluctuation is 85% to 110% of the

control supply voltage. (see note)

Influence of frequency

±

3% max. (at 

±

5% of rated frequency)

Insulation resistance

10 M

 min. (at 500 VDC) between electric circuits and mounting panel

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min between electric circuits and mounting panel

Overcurrent

20 times of max. set value of operating current for 2 s

Vibration resistance

Destruction: 16.7 Hz, 1-mm double amplitude for 10 min each in X, Y, and Z directions

Shock resistance

Destruction: 100 m/s

2

 (approx. 10G)

Ambient temperature

Operating: –10

°

C to 55

°

C (with no icing)

Ambient humidity

Operating: 45% to 85%

Weight

K2CU-F: approx. 390 g; K2CU-P: approx. 300 g

Note:

The logical value is an operating value within a range of 0.85 to 1.1 with a voltage fluctuation of 85% to 110%, based on the value at the
control supply voltage measured as 1.

Summary of Contents for K2CU -

Page 1: ...CU F80A CGS 110 VAC compensation K2CU F10A DGS K2CU F20A DGS K2CU F40A DGS K2CU F80A DGS 200 VAC K2CU F10A EGS K2CU F20A EGS K2CU F40A EGS K2CU F80A EGS 220 VAC K2CU F10A FGS K2CU F20A FGS K2CU F40A FGS K2CU F80A FGS K2CU F Large capacity Built in Current Transformer Models Control supply voltage Operating current 4 to 10 A 8 to 20 A 16 to 40 A 32 to 80 A 100 VAC With voltage fluctuation K2CU F10A...

Page 2: ...Repeat accuracy 3 max Influence of temperature 10 max at 20 C 30 C Influence of voltage Models without voltage fluctuation compensation 3 max of the value measured at the control supply voltage on condition that the voltage fluctuation is 85 to 110 of the control supply voltage Models with voltage fluctuation compensation 5 max of the logical value on condition that the voltage fluctuation is 85 t...

Page 3: ...wo detector sections operating independently If either of the input signals from the CTs is lower than the reference value the output relay and alarm indicator will be activated The K2CU FjjA jGS incorporates a voltage fluctuation com pensation function which automatically corrects the reference value if the supply voltage fluctuates Current voltage converter Smoothing circuit Gate circuit Setting...

Page 4: ...Ts is lower than the reference value the output relay and alarm indicator will be activated The K2CU F incorporates a voltage fluctuation compensation func tion which automatically corrects the reference value if the supply voltage fluctuates Current voltage converter Smoothing circuit Setting circuit Reference voltage generator Power circuit Current voltage converter Smoothing circuit BZ Output c...

Page 5: ...ue Normal current abnormal current 2 Knob Red point indicates the set value Heater Connection and Current The following table shows the different connections possible The formula under each illustration indicates the electrical current value of the heater elements under normal and abnormal conditions Phase Normal condition Abnormal condition Single phase 200 V 5 A 5 A 1 kW 200 V 0 A 0 A Three phas...

Page 6: ...SW1 and SW2 turned on Confirm that the alarm indicator remains off Turn off SW2 and confirm that the alarm indicator comes on and that the output relay operates Turn on SW1 set the operating current to be 0 9 times the heater cur rent and confirm that the alarm indicator goes off and the output relay releases Turn off SW1 and confirm that the alarm indicator comes on and that the output relay oper...

Page 7: ...dow type Current Transformer of the heater burnout detector Close the SW2 with switch SW1 turned on Confirm that the alarm indicator remains off Turn off SW1 and confirm that the alarm indicator comes on and that the output relay operates G K2CU F Heater SSR SW2 SW1 G S1 S2 K2CU F K2CU P The operation of the heater burnout detector can be easily checked as follows In a Single phase Circuit Set the...

Page 8: ...rm indicator remains off Turn off SW1 and confirm that the alarm indicator comes on and that the output relay operates Heater S1 S2 K2CU F SW1 Contactor In a Three phase V Network 1 Set the operating current to be 0 3 to 0 35 times the heater current Close the contactor with switch SW1 turned on Confirm that the alarm indicator remains off Turn off SW1 and confirm that the alarm indicator comes on...

Page 9: ...tted lines indicate the line con ductor passing through the round window of the current transformer Note Determine the value of R according to the specifications of the K2CU to be used The dotted line indicates the connection at a supply voltage of 100 or 110 VAC K2CU F K2CU P Dimensions Note All units are in millimeters unless otherwise indicated K2CU P Connecting Socket K2CU P 8PFA1 108 89 7 8 5...

Page 10: ...CU F on a flat surface 2 When solderless terminal lugs are desired use ones having an outer diameter of 6 5 mm maximum Installation External Connections K2CU F A GS Single phase Heater Three phase Heater G G S1 S2 b1 CM1 a1 SSR Y BZ L Y a Heater K2CU F G G S1 S2 b1 CM1 a1 Y BZ L SSR Temperature sensor Y a Heater K2CU F Temperature controller Temperature controller Power source Power source Control...

Page 11: ...ller Power source Control contact Control contact Contactor Contactor Temperature sensor Temperature sensor Three phase V connected Heater With External Current Transformer S1 S2 b1 CM1 al Heater K2CU F S1 S2 b1 CM1 al Heater K2CU F10A j Power source CT jA SA CT jA SA Note Pass two out of the three line conductors through the current transformers of the heater burnout detector twice as shown ...

Page 12: ...the two lines through the openings of the heater burnout detector When a three phase heat er is used pass two phases of the three lines through the open ings In either case if only one line passes through an alarm signal will always be produced With single phase power supply With three phase power supply Heater Heater Pass the lines through the openings only once If they are passed more than once ...

Page 13: ...al and 100 V or 110 V terminal or the 0 V terminal and 200 V or 220 V terminal of the K2CU P otherwise the K2CU P will not operate Operating Current Setting when Several Heaters are Used The following table shows relative values of changes in the current when any one of several heaters connected in parallel has burned out The current value under normal condition is 1 Use this table as a guideline ...

Page 14: ...a 540 Japan Phone 06 949 6014 Fax 06 949 6028 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No N39 E1 2 In the interest of product improvement specifications are subject to change without notice Printed in Japan 0393 1M 0393 ...

Reviews: