K8AK-AW

6

Timing Charts

Overcurrent and Undercurrent Operation 

Diagram

DIP switch settings: SW3 ON and SW4 ON, or SW3 OFF and SW4 

OFF

Overcurrent and Overcurrent Operation 

Diagram (Overcurrent Pre-alarm Mode)

DIP switch settings: SW3 ON and SW4 OFF.

Undercurrent and Undercurrent Operation 

Diagram (Undercurrent Pre-alarm Mode)

DIP switch settings: SW3 OFF and SW4 ON.

Input

Note 1. The K8AK-AW

@

 output contacts are normally operative.

Note 2. The startup lock prevents unnecessary alarms from being generated during the 

unstable period when the power is first turned ON. There is no contact output 
during timer operation.

t

Flashing

Lit

Flashing

Lit

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

AL1 alarm indicator

AL2 alarm indicator

Overcurrent (AL1) 

contacts (11-14)

Undercurrent (AL2) 

contacts (21-24)

Overcurrent 

set value (AL1)

Undercurrent 

set value (AL2)

Power 

supply voltage

t: Operating time (0.1 to 30 s)

LOCK

LOCK: 
Startup lock time 
(0 to 30 s)

t

t: Operating time (0.1 to 30 s)

Delay: 250 ms
 (reference value)

Delay: 250 ms 
(reference value)

Note 1. The K8AK-AW

@

 output contacts are normally operative.

Note 2. The startup lock prevents unnecessary alarms from being generated during the 

unstable period when the power is first turned ON. There is no contact output during 
timer operation.

Flashing

Lit

Flashing

Lit

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

AL1 alarm indicator

AL2 alarm indicator

Overcurrent (AL1) 

contacts (11-14)

Overcurrent 

set value (AL2)

Overcurrent (AL2) 

contacts (21-24)

Overcurrent 

set value (AL1)

Input

Power 

supply voltage

LOCK: 
Startup lock time 
(0 to 30 s)

LOCK

t: Operating time (0.1 to 30 s)

t

t: Operating time (0.1 to 30 s)

t

Delay: 250 ms 
(reference value)

Delay: 250 ms 
(reference value)

Note 1. The K8AK-AW

@

 output contacts are normally operative.

Note 2. The startup lock prevents unnecessary alarms from being generated 

during the unstable period when the power is first turned ON. There is no 
contact output during timer operation.

Lit

Flashing

Lit

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

AL1 alarm indicator

AL2 alarm indicator

Undercurrent (AL1) 

contacts (11-14)

Undercurrent 

set value (AL2)

Input

Undercurrent (AL2) 

contacts (21-24)

Undercurrent 

set value (AL1)

Power 

supply voltage

LOCK: 
Startup lock time 
(0 to 30 s)

LOCK

Flashing

t: Operating time (0.1 to 30 s)

t

t: Operating time (0.1 to 30 s)

t

Delay: 250 ms 
(reference value)

Delay: 250 ms 
(reference value)

Summary of Contents for K8AK-AW Series

Page 1: ...ent Transformer CT Direct input is not possible Accessory Order Separately OMRON CT Commercially Available CTs If you use a commercially available CT do not exceed the overload capacity of the K8AK AW...

Page 2: ...mA AC DC 50 to 500 mA AC DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 0 to 100 mA AC DC I2 COM Approx 1 Direct input 0 to 500 mA AC DC I3 COM Approx 0 2 Direct input K...

Page 3: ...puts ALM Red Input impedance Refer to Input Range on previous page Output relays Two SPDT relay outputs normally closed operation Output relay ratings Rated load Resistive load 5 A at 250 VAC 5 A at 3...

Page 4: ...minals Between input terminals and output terminals Dielectric strength 2 000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals Between power su...

Page 5: ...er CT Wiring Example Directly Inputting a Current Using a CT K8AK AW1 100 240VAC A B Control Output Relay output 250 VAC 5 A resistive load 30 VDC 5 A resistive load A Current Input AW1 Relay Output C...

Page 6: ...operative Note 2 The startup lock prevents unnecessary alarms from being generated during the unstable period when the power is first turned ON There is no contact output during timer operation Flash...

Page 7: ...nal block See notes 1 and 2 Alarm indicator Current knob AL2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when relay is operating Alarm...

Page 8: ...ched the same level Use this as a guide to set the current The maximum setting range will differ depending on the model and the input terminal Example K8AK AW3 Using Input Terminals I3 COM The maximum...

Page 9: ...de to set the startup lock time The startup lock time will start when the input current reaches 30 or more of the set value Use startup lock time to prevent unwanted operation e g as a result of inrus...

Page 10: ...figure for information on the motor startup current For a motor with a rating of 5 A the startup current will be approximately 30 A The startup current will exceed the overload capacity rating 150 for...

Page 11: ...cified torque of 0 49 to 0 59 N m Use of the product beyond its life may result in contact welding or burning Make sure to consider the actual operating conditions and use the product within its rated...

Page 12: ...ifficult to see 15 Do not use the product if it is accidentally dropped The internal components may be damaged 16 Be sure you understand the contents of this catalog and handle the product according t...

Page 13: ...MEMO 13...

Page 14: ...MEMO 14...

Page 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 16: ...A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Tokyo JA...

Reviews: