background image

1

New Product

Three-phase Voltage, Asymmetry, and Phase-sequence Phase-loss Relay

K8DT-PZ

Protect motors and other equipment from unstable 
voltages in the power supply system.
Detect overvoltages, undervoltages, voltage 
asymmetry, phase sequence, and phase loss for 
three-phase power supplies.

• Phase loss detection while the motor is operating.
• Global power supply support. (Changed with a switch.)
• Greater resistance to inverter noise.
• Width of 17.5 mm to reduce space required in panels.
• Push-In Plus Terminal Blocks that reduce wiring work.

The use of cage clamps enables wiring with bare stranded wires.
Double-insertion holes for crossover wiring (all terminals).

• UL listed for easy shipping to North America.
• Certification is pending for LR standards.
• Models added with transistor outputs for superior contact reliability.

Ordering Information

Three-phase Voltage, Asymmetry, and Phase-sequence Phase-loss Relay

Note:

The input range is set with a rotary switch.

*

The power supply voltage is the same as the rated input voltage.

Options (Order Separately)

Front Cover

Refer to 

Safety Precautions

 on page 9.

Refer to pages 7 to 8 for commonly asked questions.

For the most recent information on models 
that have been certified for safety 
standards, refer to your OMRON website.

Rated input voltage 

*

Output

Model

3-phase 3-wire mode 200, 220, 230, 240 VAC

Relay: SPDT contact output

K8DT-PZ1CN

Transistor: NPN output

K8DT-PZ1TN

3-phase 3-wire mode 380, 400, 415, 480 VAC

Relay: SPDT contact output

K8DT-PZ2CN

Transistor: NPN output

K8DT-PZ2TN

Appearance

Model

Y92A-D1A

Summary of Contents for K8DT-PZ Series

Page 1: ...easy shipping to North America Certification is pending for LR standards Models added with transistor outputs for superior contact reliability Ordering Information Three phase Voltage Asymmetry and Ph...

Page 2: ...h no condensation or icing Storage temperature 25 to 65 C with no condensation or icing Ambient operating humidity 25 to 85 RH with no condensation Storage humidity 25 to 85 RH with no condensation Al...

Page 3: ...Fixed at 2 Lit Flashing Lit Flashing Lit Flashing L1 Input L2 L3 Alarm indicator Contacts 11 14 or transistor output Lit Lit Lit L2 L1 L3 Flashing Asymmetry set value Delay time 250 ms reference value...

Page 4: ...s designed only to output a signal when an error is detected Power indicator Output status indicator Asymmetry rate knob ASY Overvoltage undervoltage knob OV UV Operating time knob T Alarm indicator T...

Page 5: ...o 10 the asymmetry operating voltage would be 20 V and an alarm would be output when the difference between the highest and lowest phase to phase voltages exceeds 20 V Overvoltage Undervoltage Overvol...

Page 6: ...phase Voltage Asymmetry and Phase sequence Phase loss Relays K8DT PZ1 K8DT PZ2 Options Order Separately Front Cover Y92A D1A 52 7 3 5 1 8 17 5 5 85 DIN Tracks PFP 100N PFP 50N Dimensions in parenthes...

Page 7: ...DT terminals is 120 of the set value for overvoltage detection 80 of the set value for undervoltage detection or equal to or greater than the asymmetry operating value when the auxiliary relay in conn...

Page 8: ...ed because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light To detect motor load phase loss during operation use the undervoltage detectio...

Page 9: ...alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay regularly To maintain s...

Page 10: ...e terminal block may be damaged 25 Insert a flat blade screwdriver into the release holes at an angle The terminal block may be damaged if the screwdriver is inserted straight in 26 Do not allow the f...

Page 11: ...he release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short circuit...

Page 12: ...rced insulation defined in IEC 60664 that is suitable for the maximum applied voltage for the clearance solid insulation and other factors There is basic insulation between the input terminals and out...

Page 13: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 14: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...