background image

K8DT-PZ

3

Connections

Terminal Diagram

Note:

Do not connect anything to terminals that are shaded in gray.

Wiring Example

Relay Output

Transistor Output

Note:

Use copper wires with a rating of 75°C or an equivalent rating.

Timing Charts

Overvoltage, Undervoltage, Phase Sequence, and Phase Loss Operation Diagram

Inside

Inside

(2) Output

C: Relay Output

T: Transistor Output

14

11

12

14

11

(1) Input Voltages

3-phase,
3 W
power
supply

Phase-to-phase voltage:
 200 to 240 VAC

PZ1

PZ2

L1

L3

L2

3-phase,
3 W
power
supply

Phase-to-phase voltage:
 380 to 480 VAC

L1

L3

L2

K8DT-PZ1 C N

(1) (2)

L1

14

L2

11

12

L3

DIP SW

3-phase

voltage

Motor

Power 
supply 
AC/DC

L1

L2

L3

DIP SW

L1

14

L2

11

12

L3

PLC

Moter

Power
supply

AC/DC

L1

L2

L3

DIP SW

L1

14

L2

11

L3

3-phase

voltage

L1

L3

L2

L3

L2

L1

Flashing

Flashing

L1

L2

L3

Phase Loss Operation

Phase sequence Operation

t: Operating time (0.1 to 30 s)

t: Operating time (0.1 to 30 s)

t1: Power ON lock (1 s)

t

t: Operating time (0.1 to 30 s)

t

t1

t

Alarm indicator

Undervoltage set value

Overvoltage set value

Contacts 11-14 or 

transistor output

L1

L2

Input

L3

Hysteresis: Fixed at 2%

Hysteresis: Fixed at 2%

Hysteresis: Fixed at 2%

Lit

Flashing

Lit

Flashing

Lit

Flashing

L1

Input  L2

L3

Alarm indicator

Contacts 11-14 or 

transistor output

Lit

Lit

Lit

L2

L1

L3

Flashing

Asymmetry set value

Delay time: 250 ms 
(reference value)

Delay time: 250 ms 
(reference value)

Delay time: 250 ms
 (reference value)

Operation Table

*1.

L1 and L2 are also used for the power supply. If the 

voltage becomes very low, the indicator will turn OFF.

*2.

The indicator will flash once per second after an 

incorrect phase is detected and once per 0.5 second 

during the detection time.

Item

Indicators

Output

operation

OUT_LED

ALM_LED

Normal

ON

OFF

ON

Overvoltage

OFF

ON

OFF

Undervoltage

OFF

ON

OFF

Asymmetry

OFF

ON

OFF

Phase loss

OFF

ON *1

OFF

Phase 
sequence

OFF

Flashing *2

OFF

Note: 1.

The K8DT-PZ

@

 output contacts are normally operative.

2.

The power ON lock prevents unnecessary alarms from being generated 

during the unstable period when the power is first turned ON. There is no 

contact output during timer operation.

3.

Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected 

when any of the phase-to-phase voltages goes below 60% of the rated input.

4.

L1 and L2 are also used for the power supply. If the voltage becomes very 

low, the Relay will not operate.

5.

Phase loss (on power supply side and load side) is not detected in the motor 

load during operation.

Summary of Contents for K8DT-PZ Series

Page 1: ...easy shipping to North America Certification is pending for LR standards Models added with transistor outputs for superior contact reliability Ordering Information Three phase Voltage Asymmetry and Ph...

Page 2: ...h no condensation or icing Storage temperature 25 to 65 C with no condensation or icing Ambient operating humidity 25 to 85 RH with no condensation Storage humidity 25 to 85 RH with no condensation Al...

Page 3: ...Fixed at 2 Lit Flashing Lit Flashing Lit Flashing L1 Input L2 L3 Alarm indicator Contacts 11 14 or transistor output Lit Lit Lit L2 L1 L3 Flashing Asymmetry set value Delay time 250 ms reference value...

Page 4: ...s designed only to output a signal when an error is detected Power indicator Output status indicator Asymmetry rate knob ASY Overvoltage undervoltage knob OV UV Operating time knob T Alarm indicator T...

Page 5: ...o 10 the asymmetry operating voltage would be 20 V and an alarm would be output when the difference between the highest and lowest phase to phase voltages exceeds 20 V Overvoltage Undervoltage Overvol...

Page 6: ...phase Voltage Asymmetry and Phase sequence Phase loss Relays K8DT PZ1 K8DT PZ2 Options Order Separately Front Cover Y92A D1A 52 7 3 5 1 8 17 5 5 85 DIN Tracks PFP 100N PFP 50N Dimensions in parenthes...

Page 7: ...DT terminals is 120 of the set value for overvoltage detection 80 of the set value for undervoltage detection or equal to or greater than the asymmetry operating value when the auxiliary relay in conn...

Page 8: ...ed because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light To detect motor load phase loss during operation use the undervoltage detectio...

Page 9: ...alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay regularly To maintain s...

Page 10: ...e terminal block may be damaged 25 Insert a flat blade screwdriver into the release holes at an angle The terminal block may be damaged if the screwdriver is inserted straight in 26 Do not allow the f...

Page 11: ...he release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short circuit...

Page 12: ...rced insulation defined in IEC 60664 that is suitable for the maximum applied voltage for the clearance solid insulation and other factors There is basic insulation between the input terminals and out...

Page 13: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 14: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...

Reviews: