95
6
. Detailed settings for communications
6.4 Address map (continued)
●
Parameter area list
Address
Type
Item
R/W
CompoWay/F
Modbus RTU
1000
2000
Unit Individual setting
Phase and wire type
H'00000000 : 1P2W
H'00000001 : 1P3W
H'00000002 : 3P3W
H'00000003 : 1P2W2
H'00000004 : 1P3W2
H'00000005 : 3P4W
R/W
1001
2002
Communication address
00 to 99 : CompoWay/F
01 to 99 : Modbus RTU
R
1008
2010
Pulse output ON/OFF
0 : OFF
1 : ON
R/W
1009
2012
Voltage selected
0 : V_R
1 : V_T
2 : V_R-T
R/W
100A
2014
CT secondary side current
H'00000000 : 1A
H'00000001 : 5A
R/W
100B
2016
CT primary side current
x1 value of amperage
1 to 9999
R/W
1100
2200
Common settings
Protocol
0 : CompoWay/F
1 : Modbus
R/W
1101
2202
Communication speed
0 : 1200bps
1 : 2400bps
2 : 4800bps
3 : 9600bps
4 : 19200bps
5 : 38400bps
R/W
1102
2204
Data length
0 : 7bit
1 : 8bit
R/W
1103
2206
Stop bit
0 : 1bit
1 : 2bit
R/W
1104
2208
Parity
0 : NONE
1 : ODD
2 : EVEN
R/W
1105
220A
Transmission wait time
Unit: ms
0 to 99
R/W
1106
220C
Pulse output units
0 : 1Wh
1 : 10Wh
2 : 100Wh
3 : 1kWh
4 : 5kWh
5 : 10kWh
6 : 50kWh
7 : 100kWh
R/W