83
6
. Detailed settings for communications
6.3 CompoWay/F (continued)
●
List of response codes
When normal end
When an error occurs
code
Name
Description
Priority
0000
Normal end
No error.
None
code
Name
Description
Priority
0401
Unsupported command
This is an unsupported service function.
1
1001
Over command length
The command length is too long.
2
1002
Insufficient command length
The command is not long enough.
3
1003
Mismatched element and data
numbers
There is a mismatch between the number of
elements and the number of pieces of data.
6
1100
Parameter error
The parameter value is unsupported.
8
1101
Area type error
An unsupported area type has been specified.
4
1103
Start writing address out of range
error
The value of the start writing address is out of
range.
5
110B
Response length too long
The length exceeds the communications
buffer.
7
2203
Operation error
Cannot process the command.
10
3000
Status error (error is occurring)
The unit is malfunctioning.
11
3003
Read only
Writing to the variable area.
9