. Detailed settings for communications
6.4 Address map
●
List of variable areas (measurement values)
Used when remotely controlling the unit.
address
Type
Item
R/W
CompoWay/F
Modbus RTU
0000
0000
Measured value
(momentary)
Voltage V1 (voltage x 10)
R
0001
0002
Voltage V2 (voltage x 10)
R
0002
0004
Voltage V3 (voltage x 10)
R
0003
0006
Current I1 (amperage x 1000)
R
0004
0008
Current I2 (amperage x 1000)
R
0005
000A
Current I3 (amperage x 1000)
R
0006
000C
Power factor (0 to 1 x 100 (1-100))
R
0007
000E
Frequency (Hertz x 10)
R
0008
0010
Effective power (total) (Watt x 10)
R
0009
0012
Reactive power (total) (Watt x 10)
R
000A
0014
Voltage V1-V2 (voltage x 10)
R
000B
0016
Voltage V1-V3 (voltage x 10)
R
000C
0018
Voltage V2-V3 (voltage x 10)
R
000D
001A
Effective power 1 (Watt x 10)
R
000E
001C
Effective power 2 (Watt x 10)
R
000F
001E
Effective power 3 (Watt x 10)
R
0010
0020
Reactive power 1 (Watt x 10)
R
0011
0022
Reactive power 2 (Watt x 10)
R
0012
0024
Reactive power 3 (Watt x 10)
R
0100
0200
Measured value
(integration)
Unable to reset
Integrate effective energy (Wh)
R
0101
0202
Integrate regenerative energy (Wh)
R
0102
0204
Integrated reactive energy of advance (Wh)
R
0103
0206
Integrated reactive energy of delay (Wh)
R
0104
0208
Integrated total reactive energy (Wh)
R
0105
020A
Integrated T1 effective energy (Wh)
R
0106
020C
Integrated T2 effective energy (Wh)
R
0107
020E
Integrated T3 effective energy (Wh)
R
0108
0210
Integrated T4 effective energy (Wh)
R
0110
0220
Measured value
(integration 2)
Unable to reset
Integrate effective energy (kWh)
R
0111
0222
Integrate regenerative energy (kWh)
R
0112
0224
Integrated reactive energy of advance (kWh)
R
0113
0226
Integrated reactive energy of delay (kWh)
R
0114
0228
Integrated total reactive energy (kWh)
R
0115
022A
Integrated T1 effective energy (kWh)
R
0116
022C
Integrated T2 effective energy (kWh)
R
0117
022E
Integrated T3 effective energy (kWh)
R
0118
0230
Integrated T4 effective energy (kWh)
R