3-151
3 Functions of NB-Designer
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
3-6 P
a
rt
s
3
3-6-19
Data Log
Process of adding one Data Log component
1
Press the Data Log component icon, drag it to the screen, then the [Basic Properties] dialog
box of the Data Log component will pop up.
Read Address:
Refers to the word address of PLC corresponding to the 1
st
line data. And the
word address corresponding to the 2
nd
line is “Read A 1”, and the 3
rd
line is “Read A 2” and so on.
Address:
Refers to the first address of the word address corresponding to the Data Log.
Word Length:
It is determined by the sampling channels and the storage format for each
channel. When the stored style of all the channel is signed 16-bit, if the channel
number is N (where, 1<=N<=16), the Word Length will be N.