3 Functions of NB-Designer
3-220
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
Process of adding Data Transmission
1
Drag the Data Transmission icon to the screen after it being pressed, then the [Data
Transmission Property] dialog box will pop up.
Memory Type:
The Memory Type which is transmitted should be selected among [Bit] (bit
data) or [Word] (word data).
Data Length:
The number of data transferred by the Data Transmission component. When the
Memory Type is Bit or Word, the units are “bit” or “word” respectively. A
maximum 2000 partitions of data can be specified.
Source Address:
Sets the source address of the transferred data.
Destination Address:
Sets the destination address of the data transmission.
Indirect Reference:
Set this parameter when setting indirectly the source address, destination
address, and data length.
Take the following settings as example, i.e. the source address, destination address and data
length use the Indirect Reference.
After setting the source address type to “D memory” and making the source address offset
controlled by the LW100, set the destination address type to “LW memory” and make the
destination address offset and the data length controlled by the LW101 and LW102
respectively.
Summary of Contents for NB10W-TW01B
Page 4: ......
Page 10: ...Terminology 6 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 528: ...8 Web Interface 8 10 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 544: ...Appendices A 16 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 546: ...Revision 2 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 547: ......