3-255
3 Functions of NB-Designer
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
3-8 Pr
o
ject D
atab
ase
3
3-8-5 PLC
Control
(3) Read A 2: Specify the offset of the transmitted data address of the PLC side. The
offset is specified from the address of [Specified Read A 4].
For example, if the Read Address set in the PLC General Control is LW100, and the data
contained in memory LW102 is 4. The starting address of the transmitted PLC data is
LW108 = [(100 + 4) + 4].
(4) Read A 3 : Specify the offset of the transmitted data address at the sides of local
memory (LW) of the PT or Recipe data memory (RW)
In the example listed above, if the data contained in LW103 is 100, the starting address of
the transmitted PT data operated during the transmission is RW (LW)100=(0 + 100).
Here is the procedure which uses the PLC control, to transmit the data includes 30 words
starting from D100, to the data block of the same size starting from RW200 in the Recipe Data
memory of the PLC.
(1) Firstly, specify the PLC control component set with [General-purpose PLC Control] for the
control select and D10 for [Read Address].
(2) Secondly, specify the size of the data and the offset address of the controlling data. D11 is
specified to 30 (it means the number of transmitted words is 30 words.) D12 is specified to
86 (the starting address is DM100=(14+86) in the PLC and D13 is specified to 200 (the
destination address is RW200=(0+200), respectively.
(3) Finally, specifying the execute type code according to the direction of the data transmission
allows the data transmission. If D10 is specified to 1, the number of the specified data will
be transmitted from the starting address of the PLC to the Recipe Data memory of the PT. If
D13 is specified to 3, the direction to transmit the data will be reversed.
The other transmission to two destinations are performed in the same procedure as above.
4
Backlight Off
This operation uses one bit address to control the closing of the backlight, and when the bit
address is ON, the backlight will be closed.
In the settings shown as above, when LB0 is ON, the backlight turns off. In this case, when the
user touches the PT, the backlight will automatically light on, and at this time the LB0 is still ON.
If the user touches the LB0 again, it will be turned OFF, thus returning to the state before the
backlight is closed.
Summary of Contents for NB10W-TW01B
Page 4: ......
Page 10: ...Terminology 6 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 528: ...8 Web Interface 8 10 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 544: ...Appendices A 16 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 546: ...Revision 2 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 547: ......