3-327
3 Functions of NB-Designer
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
3-11 Ad
dres
s of
S
y
stem
Memo
ry
3
3-11-3
Non
v
olatile Local W
ord (L
W10000~10255)
9506~9507
Authority setting
Double-words and 32 authorities’ assignments.
LW9506 to LW9507 corresponds to 32 authorities (No.
0 to No. 31) and LW.B corresponds to each bit in
LW9506 to LW9507. For example: LW.B 9506.0
represents the authority of No. 0; and LW.B 9506.A
represents the authority of No. 10 (write).
9508~9509
Automatic Logout Time setting
Sets the unit of automatic logout time to minute during
the addition of user information (write).
9510~9511
Password Confirm
Inputs the password again for consistency confirmation
during the addition of user information (write).
9520~9521
Curser position
Refers to the curser position (X
,
Y) in input component
(read).
9535
The multiplication factor of the
communication time for the Macro
instruction
If it is specified to “N”, the maximum communication
time of the Macro external value is N times as long as
the default (read/write).
9536
The multiplication factor of the
communication time for writing operation
by the data transmission component
If it is specified to “N”, the maximum communication time
for writing operation by the data transmission
component is N times as long as the default (read/write).
9551~9554
Notifying error information
Each bit corresponds to each error information. When
the bit turns ON, the bit indicates that the corresponded
error information occurs. Refer to 3-11-4 System
Information Table (Page 3-329) in
NBDesigner
Operation Manual
for details (read).
9800~9801
Error code of the triggering error
(read/write)
3-11-3 Nonvolatile Local Word (LW10000~10255)
RTC
Addresses
Descriptions
Comments
10000
RTC (second)
BIN code with effective value ranging from 0 to 59
(read/write)
10001
RTC (minute)
BIN code with effective value ranging from 0 to 59
(read/write)
10002
RTC (hour)
BIN code with effective value ranging from 0 to 23
(read/write)
10003
RTC (day)
BIN code with effective value ranging from 0 to 31
(read/write)
10004
RTC (month)
BIN code with effective value ranging from 1 to 12
(read/write)
10005
RTC (year)
BIN code with effective value ranging from 1971 to
2037 (read/write)
10006
RTC (week)
BIN code with effective value ranging from 0 to 6
(read/write)
Description of RTC:
Users can use the related “Component” to display the time. Pay attention to the effective range. The operation
when the values out of the effective range is not ensured.
For example: “second” can not be written as 78 (BIN), otherwise RTC will continue in sequence (78 79 80 ...),
which may result in unexpected error.
Addresses
Descriptions
Comments
Summary of Contents for NB10W-TW01B
Page 4: ......
Page 10: ...Terminology 6 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 528: ...8 Web Interface 8 10 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 544: ...Appendices A 16 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 546: ...Revision 2 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 547: ......