128
Connecting to the Host’s RS-422A/485 Port
Section 5-2
Settings at the host
The setting methods for each type of unit are described in the following.
- Connecting to a CVM1/CV-series (-EV
) CPUs
@
CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1
@
CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2
[PC system settings]
When connecting to the CVM1/CV series CPU by the NT link (1:1) method, no
particular settings are required at the PC system settings.
[Setting the front switches]
@
Host link communication method selection
(selector switch)
Set this to “RS-422A”.
@
Terminator setting (DIP SW6)
Set this switch to “ON”.
(Set terminator “ON”.)
I/O port selector switch
RS-422A
RS-232C
@
Communication type setting (DIP SW3)
Set this switch to “ON”.
(for communication by “NT link”)