84
Connecting to the RS-232C Port at the Host
Section 4-1
When Using the NT Link (1:N) Method
S
Compatible host units
The OMRON PCs that can be connected using the NT link (1:N) method are
CS1 series CS1G/H and C series C200HX/HG/HE (–Z) only.
Check the model and series of the PC against the type of CPU or communica-
tions board before making the connections.
The host units that can be connected to the NT31/NT31C by the NT link (1:N)
method using the RS-232C ports of both units are indicated in the table below.
PC
Series
CPUs with Built-in
NT Link Function
CPUs Connectable with
Expansion
Communication Board
(*1)
Connectable to
CS1
series
CS1G-CPU42/43/44/45-E
CS1H-CPU63/64/65/
66/67-E
CS1G-CPU42/43/44/
45-E
CS1H-CPU63/64/65/
66/67-E
CS1G
CS1H
C200HE-CPU42-(Z)E
C200HE-CPU32-(Z)E
(*2)
C200HE-CPU42-(Z)E
(*2)
C200HE (-ZE)
C200HG-CPU43-(Z)E
C200HG-CPU63-(Z)E
C200HG-CPU33-(Z)E
(*2)
C200HG-CPU43-(Z)E
(*2)
C200HG-CPU53-(Z)E
(*2)
C200HG-CPU63-(Z)E
(*2)
C200HG (-ZE)
C series
C200HX-CPU44-(Z)E
C200HX-CPU64-(Z)E
C200HX-CPU65-ZE
C200HX-CPU85-ZE
C200HX-CPU34-(Z)E
(*2)
C200HX-CPU44-(Z)E
(*2)
C200HX-CPU54-(Z)E
(*2)
C200HX-CPU64-(Z)E
(*2)
C200HX-CPU65-ZE
(*2)
C200HX-CPU85-ZE
(*2)
C200HX (-ZE)
*1 One of these serial communication boards, CS1W-SCB21-E or CS1W-SCB41-E, is
required.
*2 One of the following communication boards is required:
C200HW-COM02/COM04/COM05/COM06 (-EV1)
S
Settings at the host
<C-series C200HX/HG/HE (-ZE)>
[PC system setting area settings]
Write the communication conditions directly to the “PC system setting area”
(data memory) using a peripheral tool (e.g. SYSMAC support software).
For details on setting the “PC system setting area settings”, refer to the “SYS-
MAC C200HX/HG/HE (-ZE) Programming Manual” (W303-E1-
j
).
Make the settings in the words shown below according to the port used.
Connection to
Word #
Writing Value
Setting
C200HX/HG/HE (-ZE)
Built-in RS-232C port
DM6645
Communication board
Port A
DM6555
5
j
00
Use NT link (1:N)
j
= highest unit number of the
(*1)
Communication board
Port B
DM6550
connected PTs (1 to 7)
(*1)
*1 When using C200HE (-ZE), the range for PT unit numbers is 1 to 3.
Summary of Contents for NT31 Series
Page 1: ...Cat No V043 E1 2 Programmable Terminal NT31 31C OPERATION MANUAL...
Page 2: ...iii NT31 31C Programmable Terminal Operation Manual Produced March 1999...
Page 41: ...30 Before Operating Section 1 5...
Page 75: ...64 Using a Memory Unit NT31 NT31C without V1 Section 3 6...
Page 160: ...149...
Page 174: ...163...
Page 193: ...182...
Page 211: ...200...
Page 235: ...224 c Return to the screen on which screens are specified...
Page 262: ...251...
Page 360: ...349 It is not possible to control a gloval window by touch switch operation...
Page 468: ...457 254 255 0 2 7 1 4 5 3 3 0 0 0 5 9 8 0 3...
Page 476: ...465 Special Functions Section 7 16...
Page 495: ...484 OFF...
Page 610: ...599 Commands Responses Section 9 3...
Page 630: ...619 Examples of Actual Applications of Memory Link Section 10 2...