6-2
Service Data
This section lists the service data that are supported by the IO-Link I/O Hubs.
6-2-1
Digital I/O Hub
The following shows the service data of the Digital I/O Hubs.
IO-Link Interface Standards
Index
(Dec)
Subin-
dex
(Dec)
Item
Back-
up
Format
Ac-
cess
Data
length
(Byte)
Default
value
Selectable
range
Remarks
2
0
System-Com-
mand
---
UInteger W
1
---
05 hex:
Parameter
upload start
82 hex:
Restore
factory set-
ting
---
16
0
Vendor Name
---
String
R
20
OMRON
Corpora-
tion
---
---
17
0
Vendor Text
---
String
R
20
OMRON
Corpora-
tion
---
---
18
0
Product Name
---
String
R
20
---
Each product
model
19
0
Product ID
---
String
R
20
---
Each product
model
20
0
Product Text
---
String
R
20
IO-Link I/O
Hub
---
---
21
0
Serial Number
---
String
R
16
---
---
---
22
0
Hardware Ver-
sion
---
String
R
4
---
---
---
23
0
Firmware Ver-
sion
---
String
R
4
---
---
---
24
0
Application
Specific Tag
¡
String
R/W
32
32 aster-
isks
---
---
37
0
Detailed Device
Status
---
Record
R
30
---
---
---
40
0
Process Data
Input
---
PD In
R
20
---
---
Only for IO-
Link I/O Hub
with an input
41
0
Process Data
Output
---
PD Out
R
2
---
---
Only for IO-
Link I/O Hub
with an output
*1.
The “
¡
” indicates that the data is backed up. The “---” indicates that the data is not backed up.
*2.
The values are as follows:
6 Process Data and Service Data
6-9
NXR-series IO-Link I/O Hub User’s Manual (W620)
6-2 Service Data
6
6-2-1
Digital I/O Hub
Summary of Contents for NXR Series
Page 6: ...Manual Structure 4 NXR series IO Link I O Hub User s Manual W620 ...
Page 26: ...Revision History 24 NXR series IO Link I O Hub User s Manual W620 ...
Page 34: ...1 Features and System Configuration 1 8 NXR series IO Link I O Hub User s Manual W620 ...
Page 90: ...6 Process Data and Service Data 6 12 NXR series IO Link I O Hub User s Manual W620 ...
Page 108: ...7 Functions of IO Link I O Hubs 7 18 NXR series IO Link I O Hub User s Manual W620 ...
Page 131: ...I Index I 1 NXR series IO Link I O Hub User s Manual W620 I ...
Page 133: ......