3
.
Operation
26
4. Displays and beeps when there is an equipment failure
ON
or
Discharging
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
18
There are too many connected
devices and the rated capacity is
exceeded
If this state continues for as long as
or longer than the times described
below, commercial power continues
to be supplied through bypass
operation (Note 1)
- When 110% or higher: Bypass
operation begins after 5 minutes
(Go to No.19)
- When 150% or higher: Output
stops immediately (Go to No.20)
Reduce the number of
connected devices until the
display appears as in status
No. 3
Note 1: In bypass operation, commercial power is output directly.
Output stops when a power failure (AC input OFF) occurs in bypass operation.
Note 2: The displays and operations vary according to the status.
Intermittent
0.5-second
intervals
ON
or
OFF
No.
Status
indicator
Beep
Output
Charging
Description
Solution
Battery
replacement
lamp
( indicates blinking)
( indicates the display is ON)
( indicates the display is OFF)
ON
or
Discharging
19
(Same as above)
Moved to bypass operation
(Note 1) because status No.17
continued
If the connection capacity is
increased further and reaches
150% or higher, output stops
immediately (Go to No.20)
Display codes
alternate with
each blink
Intermittent
0.5-second
intervals
ON
or
Discharging
21
22
23
24
25
——
——
——
——
Turn OFF this unit and all
connected devices
Then, turn the power switch
back ON for this unit only
If the display does not change,
there is a problem with this unit
Contact the shop of purchase
or our Electronic Systems &
Equipments customer support
center at: _____
Moved to bypass operation due
to output voltage error (over)
(Note 1)
Displays the details of the error that
occurred only while pressing the beep
stop switch while in state No. 22
Moved to bypass operation due
to output voltage error (under)
(Note 1)
(Same as above)
Moved to bypass operation due
to battery charge voltage error
(over)
(Same as above)
26
——
(Same as above)
27
——
(Same as above)
28
——
(Same as above)
29
——
(Same as above)
Moved to bypass operation
due to battery charge voltage
error (under)
Moved to bypass operation due
to problem with the internal
temperature (Note 1)
Stopped due to bypass bus
voltage error
(Commercial Power Mode continues)
Moved to bypass operation due
to problem with the internal
cooling fan (Note 1)
ON
or
Discharging
20
Continuous
Turn OFF the power switches of
all devices connected to the unit,
reduce the number of connected
devices, and turn the power
switch back ON again
Output stopped due to
exceeded connection capacity
Continuous
Failure occurred
(Only “EE” is blinking: Output
stopped
Blinking switches between “EE”
and “bP”: Entered bypass
operation)
When the beep stop switch is
pressed, the details of the error
are displayed (Nos. 23 to 29)
or
Display codes
alternate with
each blink
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Output stopped due to exceeded
connection capacity or a short-
circuit with the connected
devices
Check that the AC input of connected
devices is not short-circuited, or
that the connection capacity does
not exceed the rated capacity
(Note 2)