UPS functions
30
●
Setting for beeper sound in the event of power failure, etc. (setting switch 1 )
… Factory setting: OFF
OFF: The beeper sounds when an alarm is necessary.
ON: The beeper does not sound for backup operation or battery replacement. The beeper
sounds for other errors (connection capacity exceeded, operation error, etc.).
ON
ON
DIP
1 2
5
6
7
8
3 4
●
Auto startup setting after recovery from power failure (setting switch 2 )
… Factory setting: OFF
OFF: Automatically starts when power is restored.
After a power failure occurs and the unit shuts down using the shutdown software or con-
tact signal(BS signal), the unit automatically starts and begins to output when the commer-
cial power is restored.
ON: Does not automatically start when power is restored.
After the unit is shut down with the UPS monitoring software or contact signal (BS signal), it
does not start up when commercial power is restored. Startup is performed by turning the
power switch OFF once, and then back ON again.
1 2
5
3 4
8
6 7
ON
ON
DIP
●
Setting for whether or not to perform battery test (setting switch 3 )
… Factory setting: OFF
OFF: The battery test is automatically executed once every 4 weeks.
ON: Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.