5
.Measuring the backup time
40
(2) Add the values converted into W to obtain the total capacity of the connected devices.
(3) Calculate the initial value of the backup time for the total capacity of the connected devices from
the graph below.
●
Graph of backup time (graph of initial values for products that have not been used)
●
The smaller the capacity of connected devices becomes, the longer the backup time be-
comes.
* These backup times are for reference only. Times may vary according to battery life and external
environmental conditions (temperature, etc.).
0.0
20.0
40.0
60.0
80.0
100.0
120.0
140.0
160.0
0W 500W
1000W
1500W 2000W
2500W
3000W
BN220S
BN300S
BN50S
BN150S
BN100S
BN75S
Backup time
(20°C, initial value)
(Minutes)
Power consumption
of connected devices(W)
BN100S
(900W)
BN50S
(450W)
BN220S
(1980W)
20W
50W
100W
200W
300W
400W
500W
700W
1000W
1400W
BN50S
230
109
49
21
12
8.2
5.5
(at 450W)
3.5
(at 680W)
7.9
(at 900W)
5.0
(at 1350W)
7.0
(at 1980W)
-
-
-
-
-
-
-
620
290
BN75S
230
109
49
21
12
8.2
6
BN100S
140
60
35
24
18
11
BN150S
620
290
140
60 35 24 18 11 7
200W
400W
600W 800W 1000W 1200W 1400W 1600W 1800W 2000W 2700W
BN220S
150 64 38 25 18 15 12 10 8.4
BN300S
150 64 38 25 18 15 12 10 8.4 7.5 5
Time unit: Minutes
Model
Model