.Using a contact signal
74
●
BU/BL signal reverse output setting
BU and BL signals are output in reverse.
AC input
ON
OFF
ON
OFF
ON
OFF
BU signal
((setting switch 3:
OFF (normal output))
BU signal
((setting switch 3:
ON (reverse output))
ON
1 2
3
Setting switch 3
Backup signal output (BU)
OFF
Normal output (factory setting)
ON
Reverse output
●
Jumper settings
By making jumper settings, the contact signal card SC05/06 connector pin assignments can be
changed.
Turn over the contact signal card, and change the contact sugnal card’s JP2 to JP9 jumper settings (8
settings) to "SC05/06".
SC05/06
SC07
SC05/06
Jumper settings
(8 digits)
<Before change>
<After change>
SC07
* Use the [SC05/06/07] side for JP10.
* Factory settings: SC07 side for JP2 to JP9,
SC05/06/07 side for JP10
* When using the unit in the SC05 compatible
mode, use an optional BUC10 cable.
■
Setting up when using the unit in the SC05 compatible mode